Configured for relay contact switching and interlock execution in machinery protection systems, the Emerson EPRO A6740/12 (A6740/12 Output Relay Module) provides direct physical/electrical execution. It converts system logic commands into discrete contact state outputs across MMS6000 platforms.

Hardware Specifications

Parameter Specification
Model A6740/12
Brand Emerson EPRO
Base Model A6740/12
Origin Germany
Weight 320 g net (450 g packaged)
Dimensions 160 mm L x 60 mm W x 128.4 mm H
Operating Temp 0 to 65 deg C (32 to 149 deg F)
Power Consumption Rack backplane powered
Output Type 16-Channel Relay
Mounting Format DIN 41494 Eurocard (3HE/12TE)
Storage Temp -40 to 70 deg C
Humidity Tolerance 5% to 95% non-condensing
Vibration Proof 0.15 mm at 10-55 Hz, 19.6 m/s2 at 55-150 Hz (IEC 68-2-6)
Shock Resistance 98 m/s2 for 16 ms pulses (IEC 68-2-29)

4-20 mA HART Loop Protocol and Channel-to-Channel Isolation

The A6740/12 relay module features 16 discrete relay channels engineered with channel-to-channel isolation to prevent electrical interference between external switching circuits. This galvanic separation ensures that contact closures or field ground faults do not couple into adjacent control loops or 4-20 mA HART DCS instrumentation interfaces connected within the main machinery monitoring system.

Frequently Asked Questions

Q: What mounting standards and rack formats are compatible with the A6740/12 module?

A: The module conforms to the DIN 41494 Eurocard standard in a 3HE/12TE form factor, fitting standard Eurocard chassis and Emerson EPRO MMS6000 systems.

Q: What environmental shock and vibration resistance limits apply to the module?

A: The module complies with IEC 68-2-6 for vibration (0.15 mm at 10-55 Hz, 19.6 m/s2 at 55-150 Hz) and IEC 68-2-29 for shock resistance (98 m/s2 for 16 ms pulses).

Q: What wiring termination method is used for field contact connections?

A: Field connections utilize spring-clip terminal connectors to maintain wire contact retention under vibration without requiring screwed terminal maintenance.

Field Installation Guidelines

  1. Power down the designated rack slot before inserting the Eurocard module into the MMS6000 chassis.
  2. Align the module card edges with the 3HE/12TE rack guide slots and push firmly until rear connectors engage the backplane.
  3. Fasten the front panel retention screws to secure the unit against mechanical vibration and ensure frame grounding.
  4. Connect field output conductors using the spring-clip terminal connectors, verifying stripping lengths to prevent exposed leads.
  5. Ensure field relay contact load voltages and currents do not exceed maximum specified ratings before energizing loop power.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Industry 4.0 integrates digital intelligence into field operations, transforming factory automation landscapes worldwide. Spatial technologies—specifically Augmented Reality (AR) and Virtual Reality (VR)—redefine how engineers interact with industrial control systems. By bridging computer-generated CAD models with real-time operational technology (OT) data, immersive displays enable intuitive monitoring, rapid diagnostics, and safer maintenance across complex processing facilities.

Read more
Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) serve as critical quality assurance gateways in complex industrial control systems. Both procedures verify that programmable logic controllers (PLCs), distributed control systems (DCS), and associated field devices meet strict functional specifications. However, executing these tests effectively requires clear delineation between off-site staging and final field commissioning.

Read more
Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial automation relies heavily on robust networking infrastructure to connect programmable logic controllers (PLCs), distributed control systems (DCS), and human-machine interfaces (HMIs). Modern factory automation environments generate vast amounts of real-time operational data across deterministic networks. Understanding the structural differences between hubs, switches, and routers ensures optimal traffic segmentation, minimizes latency, and maintains high network availability.

Read more