The ABB CI626V1 3BSE012868R1, also cataloged as the CI626V1 Communication Interface Module, operates as a dedicated hardware component for bridging ISA bus architectures and AF100 coaxial networks within Advant OCS and System 800xA platforms.

Hardware Specifications

Parameter Specification
Model CI626V1 (3BSE012868R1)
Brand ABB
Origin Sweden
Weight 1.4 kg
Dimensions 25.4 cm x 5.1 cm x 27.9 cm
Operating Temp +5 to +55 deg C (AF100) / -40 to +70 deg C (PROFIBUS)
Power Consumption 2.5 W (24 VDC supplied via system backplane)
Communication Protocols AF100, PROFIBUS DP V1 (Master/Slave)
Transmission Rate 9.6 kbps to 12 Mbps (auto-negotiation)
Network Capacity Supports up to 80 AF100 stations
Physical Interface Integrated coaxial media modems (supports 75-ohm coaxial cabling up to 700 m)
Isolation Galvanic isolation between field modems and internal interface logic
Mounting Type DIN rail or panel mount
Protection Rating IP20

Backplane Bus Communication Velocity and Firmware Flash Compatibility

The CI626V1 module manages deterministic message routing between local controller backplanes and AF100 coaxial segments without compromising backplane bus communication velocity. Integrated hardware modems and galvanically isolated transceiver stages maintain high-speed signal integrity across distances up to 700 meters. Built-in firmware flash compatibility across Advant Master and System 800xA nodes allows seamless network expansion, ensuring predictable data update rates and reliable I/O density scaling across redundant system topologies.

Frequently Asked Questions

Q: How is power provided to the CI626V1 communication module?

A: Power is drawn directly from the host system backplane at 24 VDC, with total module power dissipation rated at 2.5 W.

Q: What physical cabling and maximum segment length are supported for the AF100 interface?

A: The onboard integrated modems connect via standard 75-ohm coaxial cable, supporting point-to-point and bus segment distances up to 700 meters.

Q: Is galvanic isolation integrated into the modem interfaces?

A: Yes, the module features galvanic isolation positioned between the coaxial modems and internal logic circuitry to suppress ground loops and electrical transients.

Field Installation Guidelines

  1. Power down the rack chassis and verify complete system electrical isolation prior to mounting or unseating the CI626V1 module.
  2. Wear an ESD wrist strap connected to cabinet earth ground when handling the board assembly.
  3. Secure the chassis onto the DIN rail or panel mounting surface, ensuring the IP20 housing latches securely in place.
  4. Attach 75-ohm coaxial cables to the integrated media modem connectors, maintaining minimum cable bend radii and ensuring proper connector shield grounding.
  5. Apply backplane power to the rack and verify network boot status via diagnostic LED indicators during initialization.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling cabinets serve as the vital interface between field instrumentation and control room electronics in modern process facilities. Regular preventive maintenance of these cabinets ensures signal integrity across programmable logic controllers (PLCs), distributed control systems (DCS), and emergency shutdown (ESD) networks. System technicians must execute structured inspection protocols to mitigate environmental risks, identify loose wiring, and maintain continuous operational readiness.

Read more
Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Industry 4.0 integrates digital intelligence into field operations, transforming factory automation landscapes worldwide. Spatial technologies—specifically Augmented Reality (AR) and Virtual Reality (VR)—redefine how engineers interact with industrial control systems. By bridging computer-generated CAD models with real-time operational technology (OT) data, immersive displays enable intuitive monitoring, rapid diagnostics, and safer maintenance across complex processing facilities.

Read more
Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) serve as critical quality assurance gateways in complex industrial control systems. Both procedures verify that programmable logic controllers (PLCs), distributed control systems (DCS), and associated field devices meet strict functional specifications. However, executing these tests effectively requires clear delineation between off-site staging and final field commissioning.

Read more