Skip to content

What are you looking for?


You may also like

Allen-Bradley MicroLogix 1400 1766-L32AWAA 32-Point AC/Relay Controller with Analog I/OAllen-Bradley MicroLogix 1400 1766-L32AWAA 32-Point AC/Relay Controller with Analog I/OAllen-Bradley MicroLogix 1400 1766-L32AWAA 32-Point AC/Relay Controller with Analog I/O
Allen-Bradley MicroLogix 1400 1766-L32AWAA 32-Point AC/Relay Controller with Analog I/O
Allen-Bradley MicroLogix 1400 1766-L32AWAA 32-Point AC/Relay Controller with Analog I/O
Allen-Bradley MicroLogix 1400 1766-L32AWAA 32-Point AC/Relay Controller with Analog I/O

Allen-Bradley MicroLogix 1400 1766-L32AWAA 32-Point AC/Relay Controller with Analog I/O


Only 10 left - Selling fast

PRODUCT SKU : 1766-L32AWAA

PRODUCT TYPE : Programmable Logic Controller

PRODUCT VENDOR : Allen-Bradley


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Module Overview

The 1766-L32AWAA is a premium, all-in-one programmable logic controller within the MicroLogix 1400 family. Designed for sophisticated small-scale automation, this "AWAA" variant distinguishes itself by combining high-voltage AC discrete I/O with embedded 12-bit analog capabilities. It features a built-in LCD for real-time diagnostics and data manipulation, along with extensive communication options including EtherNet/IP. The 1766-L32AWAA is particularly effective for HVAC, water treatment, and standalone machine control where a mix of digital sensors, relay actuators, and analog process variables (like temperature or pressure) must be managed by a single, compact device.

Detailed Engineering Specifications

The 1766-L32AWAA serves as the central intelligence of the system, offering a rich set of embedded I/O that can be further expanded via 1762 series modules.

  • Controller Type: MicroLogix 1400 (Base Unit)

  • Power Supply: 110V to 240V AC (Operating range 100–240V AC @ 47–63 Hz)

  • Digital Inputs: 20 Points (120V AC)

  • Digital Outputs: 12 Points (Relay, Normally Open)

  • Analog Inputs: 4 Channels (12-bit Voltage, 0–10V DC)

  • Analog Outputs: 2 Channels (12-bit Voltage, 0–10V DC)

  • User Memory: 20 KB (10 KB for user program / 10 KB for data)

  • Data Logging/Recipe Storage: 128 KB for logging / 64 KB for recipes

  • Communication Ports: * Port 0: 8-pin Mini DIN (RS-232/RS-485)

    • Port 1: RJ45 (EtherNet/IP, DNP3 over IP, Modbus TCP/IP)

    • Port 2: 9-pin D-Shell (Isolated RS-232)

  • Expansion Capacity: Supports up to seven (7) 1762 MicroLogix expansion modules

  • Operating Temperature: -20°C to 60°C (-4°F to 140°F)

  • Physical Weight: 2.45 lbs (1.11 kg)

Advanced Interface and Connectivity

One of the defining features of the 1766-L32AWAA is the integrated backlit LCD. This interface allows maintenance personnel to monitor I/O status, change network configurations (such as IP addresses), and modify integer values without a laptop. For networked environments, its dual serial ports and dedicated Ethernet port support multi-protocol communication, enabling the controller to act as a bridge between legacy Modbus devices and modern SCADA systems via EtherNet/IP.

Integrated Analog Capabilities

Unlike the standard AWA model, the 1766-L32AWAA includes 4 voltage inputs and 2 voltage outputs directly on the base unit. These 12-bit channels provide sufficient resolution for typical industrial feedback loops, such as regulating the speed of a Variable Frequency Drive (VFD) via the 0–10V analog output or monitoring a level sensor on the input. Because these are built-in, they do not occupy expansion slots, leaving all seven expansion positions available for additional digital, specialty, or temperature modules.

Technical FAQ

Can the analog inputs on the 1766-L32AWAA be used for 4-20mA signals?

Natively, the embedded analog ports are designed for 0–10V DC. To use a 4-20mA sensor, you must place a high-precision 500-ohm resistor across the input terminals to convert the current to a 2–10V signal, or add a dedicated 1762-IF4 analog expansion module.

Does this AC-powered model support High-Speed Counters (HSC)?

No. High-speed counting (up to 100 kHz) is only available on MicroLogix 1400 models with 24V DC inputs. The 120V AC inputs on this model are intended for standard discrete logic and do not support high-frequency pulse detection.

How is the real-time clock (RTC) maintained during power loss?

The 1766-L32AWAA includes a replaceable lithium battery (1747-BA) that maintains the RTC and the volatile RAM memory for several years under normal conditions.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Strategic Selection: Choosing the Right SCADA Software for Your PLC Project

Strategic Selection: Choosing the Right SCADA Software for Your PLC Project

In industrial automation, the SCADA (Supervisory Control and Data Acquisition) system acts as the bridge between raw machine data and actionable human intelligence. Selecting the incorrect software platform can lead to integration bottlenecks, scalability issues, and excessive long-term maintenance costs. As an automation consultant with 15 years of experience, I have guided many projects through the selection process. Below are the essential criteria for choosing a platform that ensures both performance and longevity.

Read more
Ensuring Operational Continuity: The Strategic Value of Redundant Automation Systems

Ensuring Operational Continuity: The Strategic Value of Redundant Automation Systems

In modern industrial landscapes, unplanned downtime is the ultimate adversary. For sectors relying on complex PLC and DCS architectures, a single hardware failure can trigger catastrophic production losses. Therefore, implementing redundant automation systems is no longer a luxury; it is a fundamental requirement for mission-critical operations. In this article, I analyze why redundancy remains the backbone of reliable industrial infrastructure.

Read more
Selecting the Right Cables for Industrial Automation: A Comprehensive Guide

Selecting the Right Cables for Industrial Automation: A Comprehensive Guide

Selecting the appropriate cabling infrastructure is critical for the success of any industrial automation project. Improper cable selection often leads to signal degradation, system instability, and costly downtime. As an automation engineer, I frequently see projects compromised by poor cabling choices in harsh industrial environments. This guide simplifies the complex landscape of cabling to help you make informed decisions for your PLC, DCS, and control systems.

Read more