Skip to content

What are you looking for?


You may also like

Allen Bradley 440R-D22R2 Guardmaster Dual Input Safety RelayAllen Bradley 440R-D22R2 Guardmaster Dual Input Safety RelayAllen Bradley 440R-D22R2 Guardmaster Dual Input Safety Relay
Allen Bradley 440R-D22R2 Guardmaster Dual Input Safety Relay
Allen Bradley 440R-D22R2 Guardmaster Dual Input Safety Relay
Allen Bradley 440R-D22R2 Guardmaster Dual Input Safety Relay

Allen Bradley 440R-D22R2 Guardmaster Dual Input Safety Relay


Only 10 left - Selling fast

PRODUCT SKU : 440R-D22R2

PRODUCT TYPE : Dual Input Safety Relay

PRODUCT VENDOR : Allen-Bradley


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Overview

The Allen Bradley 440R-D22R2 serves as a high-performance Dual Input (DI) Safety Relay within the Guardmaster family. This module consolidates multiple safety functions into a single 22.5mm housing, managing two dual-channel universal inputs effectively. As a 100% Brand New original component, it facilitates advanced logic configurations including AND/OR voting via a rotary switch. It interfaces seamlessly with E-stops, light curtains, and safety gates to provide deterministic protection for industrial machinery.

Technical Specifications

The 440R-D22R2 operates on a standard 24V DC architecture and supports versatile I/O interfacing.

Feature Specification
Relay Model Guardmaster Dual Input (DI)
Safety Inputs 2 Dual Channel Universal Inputs
X1 Input Terminal Single Wire Safety or OSSD (50mA)
X2 Output Terminal Single Wire Safety or OSSD (50mA)
Safety Outputs 2 N.O. (Normally Open)
Auxiliary Outputs 1 N.C. (Normally Closed) Solid State
Logic Configuration Rotary Switch (AND / OR Logic)
Power Supply 24V DC
Terminals Removable / Plug-in
Reset Modes Automatic/Manual or Manual Monitored

Engineering Advantages

  • Optimized Panel Density: The 440R-D22R2 replaces two standard safety relays by managing two independent safety circuits simultaneously. This reduces DIN rail footprint and simplifies electrical cabinet design.

  • Flexible Logic Integration: The onboard rotary switch allows engineers to toggle between AND/OR logic. This enables complex safety zoning, such as requiring two independent light curtains to be clear before allowing a machine restart.

  • Single Wire Safety (SWS) Compatibility: Terminals X1 and X2 support Single Wire Safety technology. This allows for easy expansion and linking between multiple Guardmaster relays using a single wire, drastically reducing field wiring labor and potential points of failure.

  • Simplified Maintenance: Removable terminal blocks permit rapid hardware replacement without disturbing the existing wire loom. This minimizes Mean Time to Repair (MTTR) during critical maintenance windows.

  • OSSD Interfacing: The relay directly accepts Output Signal Switching Device (OSSD) signals from sensors like laser scanners and light curtains, eliminating the need for interposing hardware.

FAQs

  • Can I use the 440R-D22R2 to monitor two separate E-stop buttons?

    Yes. The module features two universal dual-channel inputs. You can configure them to monitor two E-stops independently or link them via AND/OR logic depending on your safety protocol.

  • What is the purpose of the Solid State Auxiliary Output?

    The 1 N.C. auxiliary output provides non-safety feedback to a PLC or HMI. This allows the control system to monitor the relay status for diagnostic purposes without utilizing the primary safety contacts.

  • How do I change the reset mode from Automatic to Manual Monitored?

    You select the reset mode through the configuration settings on the front of the unit. Manual Monitored reset provides a higher level of safety by requiring a specific transition (off-to-on-to-off) to prevent unintended restarts.

  • Is this a genuine, factory-sealed unit?

    Absolutely. We supply only 100% Brand New original Allen Bradley hardware. Each unit arrives in its original factory packaging with a verifiable batch code.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Strategic Selection: Choosing the Right SCADA Software for Your PLC Project

Strategic Selection: Choosing the Right SCADA Software for Your PLC Project

In industrial automation, the SCADA (Supervisory Control and Data Acquisition) system acts as the bridge between raw machine data and actionable human intelligence. Selecting the incorrect software platform can lead to integration bottlenecks, scalability issues, and excessive long-term maintenance costs. As an automation consultant with 15 years of experience, I have guided many projects through the selection process. Below are the essential criteria for choosing a platform that ensures both performance and longevity.

Read more
Ensuring Operational Continuity: The Strategic Value of Redundant Automation Systems

Ensuring Operational Continuity: The Strategic Value of Redundant Automation Systems

In modern industrial landscapes, unplanned downtime is the ultimate adversary. For sectors relying on complex PLC and DCS architectures, a single hardware failure can trigger catastrophic production losses. Therefore, implementing redundant automation systems is no longer a luxury; it is a fundamental requirement for mission-critical operations. In this article, I analyze why redundancy remains the backbone of reliable industrial infrastructure.

Read more
Selecting the Right Cables for Industrial Automation: A Comprehensive Guide

Selecting the Right Cables for Industrial Automation: A Comprehensive Guide

Selecting the appropriate cabling infrastructure is critical for the success of any industrial automation project. Improper cable selection often leads to signal degradation, system instability, and costly downtime. As an automation engineer, I frequently see projects compromised by poor cabling choices in harsh industrial environments. This guide simplifies the complex landscape of cabling to help you make informed decisions for your PLC, DCS, and control systems.

Read more