Product Overview

The 1756-PB50 serves as a high-capacity DC power supply specifically engineered for the Allen-Bradley ControlLogix platform. It converts a nominal 24V DC input into the multiple backplane voltages required by processors, I/O modules, and communication adapters within a 1756 chassis. This module provides the necessary current for high-density configurations, ensuring stable logic-side performance across the entire backplane. We supply this unit as 100% Brand New and factory-original, guaranteeing peak electrical efficiency and system integrity.

Technical Specifications

The 1756-PB50 utilizes a robust switching architecture to maintain stable outputs even during input voltage fluctuations.

Feature Specification
Input Voltage (Nominal) 24V DC
Input Voltage Range 18–32V DC
Backplane Current Capacity (5.1V) 8A @ 50 °C / 6A @ 60 °C
Backplane Current Capacity (24V) 2.5A @ 50 °C / 2.0A @ 60 °C
Max Inrush Current 30 Amps
Isolation Voltage 250V Continuous
Hold Up Time 30ms @ 60W / 40ms @ 50W
Chassis Location Left Side (Dedicated Slot)
Weight 1.81 lbs (0.82 kg)

Engineering Advantages

  • Ride-Through Capability: The integrated capacitors provide a hold-up time of up to 40ms. This prevents nuisance controller resets during momentary DC bus brownouts or power transitions, maintaining process uptime in volatile power environments.

  • High-Density Current Delivery: This module delivers a substantial 8A at the 5.1V backplane rail. This high output supports fully populated 17-slot chassis containing multiple high-drain communication modules and processors without requiring a secondary power source.

  • Thermal Resiliency: The 1756-PB50 features advanced heat dissipation components. It operates at full capacity in ambient temperatures up to 50 °C and supports derated operation up to 60 °C, making it suitable for unconditioned industrial enclosures.

  • Direct Chassis Integration: The unit snaps directly into the dedicated power supply slot on the left side of any standard 1756 ControlLogix chassis. This design eliminates external wiring for logic power and ensures a low-impedance connection to the backplane.

FAQs

  • Can I use the 1756-PB50 in a redundant power supply configuration?

    No. The 1756-PB50 is a standard power supply. For redundant applications, you must use the 1756-PB75R or 1756-PSCA2 adapter system. This module is intended for standalone chassis power.

  • What type of fuse or circuit protection do you recommend for the input?

    To protect against the 30A inrush current and potential short circuits, install a fast-acting fuse or a high-magnetic trip circuit breaker rated appropriately for the 24V DC supply line.

  • Does this module provide power for field-side devices?

    No. The 1756-PB50 only provides power to the chassis backplane for internal module logic. You must provide a separate 24V DC source to power field-side actuators, sensors, and I/O terminal blocks.

  • How do I verify if the power supply is functioning correctly?

    The front panel includes a green "DC Power" LED. If the LED is off, check the 24V DC input terminals for voltage and ensure the module is fully seated in the chassis.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Wellhead Control Panel (WHCP) Architecture in Oil and Gas Automation

Wellhead Control Panel (WHCP) Architecture in Oil and Gas Automation

Upstream oil and gas operations rely on specialized field control platforms to manage wellhead extraction safety and hydraulic actuation. A Wellhead Control Panel (WHCP) serves as a dedicated hydraulic and pneumatic power unit designed to operate critical Christmas Tree isolation valves. By interfacing field safety components directly with Programmable Logic Controller (PLC) architecture, a WHCP protects upstream extraction assets against overpressure, catastrophic leaks, and thermal emergencies.

Read more
Understanding Marshalling Cabinets in Industrial Control Systems Architecture

Understanding Marshalling Cabinets in Industrial Control Systems Architecture

Industrial control system deployments rely on structured signal distribution to bridge field instrumentation with central processing hardware. A marshalling cabinet serves as the vital intermediate connection point between heavy field home-run multi-pair cables and delicate input/output (I/O) modules housed inside Programmable Logic Controller (PLC) or Distributed Control System (DCS) enclosures. By segregating field cable terminations from control hardware, engineers maintain system flexibility, safeguard controller components, and streamline commissioning workflows.

Read more
FAT vs SAT in Industrial Control Systems: Key Differences and Execution Guide

FAT vs SAT in Industrial Control Systems: Key Differences and Execution Guide

Industrial control system deployment relies on strict verification protocols to guarantee operational safety, system stability, and regulatory compliance. Commissioning complex Programmable Logic Controller (PLC) racks, Distributed Control Systems (DCS), and Safety Instrumented Systems (SIS) requires two critical milestones: the Factory Acceptance Test (FAT) and the Site Acceptance Test (SAT). Both procedures validate that system automation meets design specifications, but they occur at different stages of project execution and target distinct operational risks.

Read more