Product Overview

The Allen Bradley 1734-IR2E operates as a high-precision analog input expansion for the POINT I/O platform. It specializes in converting resistance signals from RTD (Resistance Temperature Detector) sensors into digital data for the controller. This module provides two independent channels for critical temperature monitoring in distributed I/O architectures. We supply this unit as 100% Brand New and Original, ensuring high-accuracy thermal feedback for your process control loops.

Technical Specifications

The 1734-IR2E utilizes high-resolution conversion technology to maintain signal integrity:

Feature Specification
Manufacturer Allen Bradley
Product Line POINT I/O (1734)
Module Type Analog RTD Input
Number of Inputs 2 High-Resolution Channels
Resolution 16-bit
Data Format Signed Integer
Isolation Voltage 50V Continuous
Power Dissipation 1.0 Watt
Thermal Dissipation 3.3 BTU/hr
Keyswitch Position 6
Operating Temp -20°C to 55°C (-4°F to 131°F)

Engineering Advantages

The 1734-IR2E solves specific thermal measurement challenges in high-density control cabinets:

  • Superior Signal Precision: The 16-bit resolution detects minute resistance changes, allowing the PLC to monitor temperature fluctuations with laboratory-grade accuracy. This precision prevents overshoot in sensitive heating or cooling applications.

  • Effective Noise Rejection: Digital filtering and 50V continuous isolation protect the low-voltage RTD signals from electromagnetic interference (EMI) generated by nearby variable frequency drives (VFDs) and motor starters.

  • Simplified Mechanical Configuration: The hardware utilizes a physical keyswitch at position 6. This mechanical lock prevents the insertion of incorrect module types into the terminal base, shielding the system from accidental voltage damage during maintenance.

  • Thermal Efficiency: The module dissipates only 1.0 Watt of power. This low thermal footprint prevents heat buildup in compact distributed I/O enclosures, extending the lifespan of adjacent electronic components.

FAQs

  • Which RTD sensor types does the 1734-IR2E support?

    This module supports standard 100-ohm Platinum (Pt) RTDs and various other resistance-based sensors. You must configure the specific sensor type (e.g., Pt 385 or Pt 3916) within the Studio 5000 or RSLogix 5000 software environment to ensure correct scaling.

  • Does this module require a specific terminal base?

    The 1734-IR2E installs into 1734-TB, 1734-TBS, or 1734-TOP terminal bases. Ensure the base is properly grounded to the DIN rail to maximize the noise rejection capabilities of the 16-bit converter.

  • How does the "Signed Integer" data format work for temperature?

    The module converts the analog resistance into a signed integer value. The PLC then scales this integer into engineering units (Celsius or Fahrenheit) based on the configuration profiles, providing direct temperature readouts to the HMI.

  • What happens if an RTD wire breaks during operation?

    The 1734-IR2E features integrated open-circuit detection. When a wire breaks or a sensor fails, the module flags a diagnostic error to the PLC, allowing the system to trigger a safe-state shutdown or alarm immediately.

 

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Hub vs Switch vs Router in Industrial Automation Architecture

Hub vs Switch vs Router in Industrial Automation Architecture

Modern factory automation relies on reliable industrial networking infrastructure to exchange real-time field data across operational technology systems. Engineers often encounter networking hardware like hubs, switches, and routers when integrating Programmable Logic Controllers, Distributed Control Systems, and SCADA monitoring nodes. Although these devices share physical ports, they operate at different layers of the Open Systems Interconnection reference model and deliver distinct traffic management capabilities.

Read more
Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling cabinets serve as the vital interface between field instrumentation and control room electronics in modern process facilities. Regular preventive maintenance of these cabinets ensures signal integrity across programmable logic controllers (PLCs), distributed control systems (DCS), and emergency shutdown (ESD) networks. System technicians must execute structured inspection protocols to mitigate environmental risks, identify loose wiring, and maintain continuous operational readiness.

Read more
Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Industry 4.0 integrates digital intelligence into field operations, transforming factory automation landscapes worldwide. Spatial technologies—specifically Augmented Reality (AR) and Virtual Reality (VR)—redefine how engineers interact with industrial control systems. By bridging computer-generated CAD models with real-time operational technology (OT) data, immersive displays enable intuitive monitoring, rapid diagnostics, and safer maintenance across complex processing facilities.

Read more