Product Overview

The Honeywell MC-PAIH03 (51304754-150) operates as a high-density High Level Analog Input (HLAI) processor within the Honeywell Process Manager architecture. This 100% Brand New and original module interfaces with 16 differential input channels, supporting a variety of voltage and current signals from 2-wire or self-powered transmitters. It converts field signals into high-resolution digital data, serving as the backbone for precision process monitoring in oil & gas, chemical, and power generation facilities.

Technical Specifications

Parameter Performance Data
Input Channels 16 Differential Channels
A/D Converter Resolution 16 Bits (14 bits utilized)
Input Ranges 0-5V, 1-5V, 0.4-2V, 4-20mA (via 250 Ω resistor)
Hardware Accuracy ± 0.075% FS (@ 23.5°C) / ± 0.15% FS (0-50°C)
Input Scan Rate 4 samples/sec per channel (250 ms window)
Input Impedance > 10 MΩ (Powered)
Common Mode Rejection 70 dB (dc to 60 Hz)
Crosstalk 60 dB (Channel-to-channel)
Max Input Voltage ± 30 Volts (No damage)
Weight 0.60 kg

Engineering Advantages

  • Superior Signal Integrity: The 70 dB Common Mode Rejection Ratio (CMRR) and integrated single-pole RC filtering mitigate electrical noise interference. This ensures stable readings even in environments with heavy electromagnetic signatures from large motors or switchgear.

  • Broad FTA Compatibility: This processor integrates seamlessly with a wide array of Field Termination Assemblies (FTAs), including MU-TAIH02, TAIH12, TAIH52, and the TAIH03/13/23/53/62 series. This flexibility allows for rapid deployment in existing infrastructure.

  • Rugged Fault Protection: The hardware withstands up to ±30V differential input without sustaining damage. This robust protective circuitry prevents module failure during field-side wiring errors or transient surges common in industrial startups.

  • High-Precision Conversion: By utilizing 14 bits of a 16-bit A/D converter, the MC-PAIH03 delivers a level of granularity essential for critical control loops where minor signal fluctuations impact product quality.

  • Standardized ANSI/IEEE Compliance: The module meets ANSI/IEEE C37.90.1-1978 surge withstand standards, providing verifiable resilience against high-voltage transients on the signal lines.

FAQs

  • Which Field Termination Assemblies (FTA) work with the MC-PAIH03?

    The MC-PAIH03 supports a broad range of FTAs including MU-TAIH02, TAIH12, TAIH22, TAIH52, TAIH62, and the newer TAIH03, TAIH13, TAIH23, and TAIH53 models. Always verify the specific terminal requirements for your transmitter type.

  • How does the module handle 4-20 mA current loops?

    The processor accepts 4-20 mA signals by passing the current through a 250 Ω precision resistor, converting the signal to a 1-5V range for the A/D converter. Ensure your FTA includes the necessary precision resistors for current loop operation.

  • What is the sampling window for the 16 channels?

    The hardware scans all 16 channels within a 250 ms window, providing 4 samples per second for every channel. This deterministic scan rate ensures synchronized data acquisition across all process points.

  • Is this a refurbished or original Honeywell part?

    We supply only 100% Brand New units in original factory packaging. This ensures the processor meets the maximum hardware accuracy of ±0.075% full-scale and carries the full operational lifespan expected of new industrial hardware.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Evolving SCADA System Architectures in Industrial Automation

Evolving SCADA System Architectures in Industrial Automation

A robust Supervisory Control and Data Acquisition (SCADA) system serves as the heartbeat of modern industrial operations. Understanding SCADA system architecture is vital for engineers designing efficient control systems. These architectures have evolved from isolated, monolithic structures to highly interconnected, networked ecosystems. Choosing the right design requires balancing data visibility, processing power, and long-term scalability requirements.

Read more
Choosing the Right Controller: PLC vs. Motion Controller in Industrial Automation

Choosing the Right Controller: PLC vs. Motion Controller in Industrial Automation

Selecting the optimal control architecture is a foundational decision in industrial automation. Engineers must frequently choose between a Programmable Logic Controller (PLC) and a dedicated Motion Controller. While both systems manage machinery, their underlying design philosophies differ significantly, impacting performance, scalability, and system integration.

Read more
Mastering PLC Power Supply Architectures and Operating Voltages

Mastering PLC Power Supply Architectures and Operating Voltages

Selecting the correct operating voltage is a critical step in designing reliable industrial automation systems. Whether you are working with a compact PLC or a large-scale DCS, your power architecture dictates the system's longevity. In this guide, we explore the standard voltage ranges and power distribution strategies required to maintain stable factory automation operations.

Read more