Overview

The Honeywell CC-PDOB01 is a 24V digital output module engineered for Experion Series C I/O systems. It provides 32 fully isolated channels capable of switching resistive and inductive loads. This module is suitable for controlling field devices, relay extensions, and automation outputs in industrial environments.

Technical Specifications

  • Manufacturer: Honeywell

  • Model Number: CC-PDOB01

  • Product Type: 24V Digital Output Module

  • IOTA Model Variants:

    • CC-TDOR01 Non-Redundant 6"

    • CC-TDOR11 Redundant 12"

    • CC-SDOR01 Relay Extension 12"

  • Number of Channels: 32 isolated

  • Contact Form: Form A (SPST/NO) or Form B (SPST/NC), jumper selectable per channel

  • Contact Material: AgSnO

  • Maximum Load Voltage: 250 VAC / 125 VDC

  • Maximum Steady-State Load Current (Resistive):

    • 3A @ 125/250 VAC

    • 3A @ 30 VDC

    • 1A @ 48 VDC

    • 0.2A @ 125 VDC

  • Maximum Steady-State Load Current (Inductive):

    • 2A @ 125/250 VAC (0.4 PF)

    • 1A @ 30 VAC (L/R =100 ms)

    • 0.3A @ 48 VAC (L/R =100 ms)

    • 0.1A @ 125 VAC (L/R =100 ms)

  • Minimum Load Voltage: 12 VDC

  • Minimum Load Current: 100 mA

  • Maximum Inrush Current: 10 A for 4s at 10% duty cycle

  • Turn-On Time: <20 ms

  • Turn-Off Time: <20 ms

  • Isolation: 1500 VAC RMS / ±1500 VDC channel-to-channel and channel-to-logic common

  • Mechanical Life: 5,000,000 cycles (@180 cycles/min)

  • Electrical Life: 50,000 cycles @6A (6 cycles/min)

  • Additional Features: Surge absorber 120 Ω + 0.033 μF per channel

Applications

  • Controlling solenoid valves, actuators, and relays in process automation

  • Integration into Experion PKS Series C distributed control systems

  • Switching both AC and DC loads with high-speed response

FAQ

Q: How many channels does the module provide?
A: The module provides 32 fully isolated digital output channels.

Q: What types of loads can it handle?
A: Supports resistive and inductive loads up to 250 VAC or 125 VDC with proper current ratings.

Q: What is the maximum turn-on/off speed?
A: Turn-on and turn-off times are both under 20 ms.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Modern manufacturing relies heavily on automated control systems to maximize throughput and maintain product quality. However, unplanned downtime in industrial automation can cost facility operators thousands of dollars per hour. Understanding how programmable logic controllers (PLCs), distributed control systems (DCS), and field instrumentation fail empowers engineering teams to implement robust preventive maintenance strategies.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

Implementing robust protection in hazardous industrial environments represents a fundamental safety requirement in factory automation. Process facilities often handle volatile gases, dusts, and chemical agents that pose significant combustion risks. Consequently, control system engineers must deploy energy-limiting interfaces to isolate safe-area control cabinets from hazardous-area field instrumentation. This article examines the function, selection, and electrical principles of intrinsic safety barriers within modern PLC and DCS networks.

Read more