Skip to content

What are you looking for?


You may also like

DC 732F 3BDH000375R0005 Digital Input/Output Module | ABBDC 732F 3BDH000375R0005 Digital Input/Output Module | ABBDC 732F 3BDH000375R0005 Digital Input/Output Module | ABB
DC 732F 3BDH000375R0005 Digital Input/Output Module | ABB
DC 732F 3BDH000375R0005 Digital Input/Output Module | ABB
DC 732F 3BDH000375R0005 Digital Input/Output Module | ABB

DC 732F 3BDH000375R0005 Digital Input/Output Module | ABB


Only 10 left - Selling fast

PRODUCT SKU : DC 732F 3BDH000375R0005

PRODUCT TYPE : Digital Input/Output Modules

PRODUCT VENDOR : ABB


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The ABB DC 732F 3BDH000375R0005, also cataloged as the DC 732F Digital Input/Output Module, operates as a dedicated hardware component for multi-channel discrete signal acquisition and field actuator driving within Freelance S700 I/O system platforms. Equipped with 32 non-redundant configurable digital input/output channels, the unit processes voltage levels with logical "0" defined from -30 V to +5 V and logical "1" from +13 V to +30 V. Powered by an external 24 VDC source drawing 0.15 A with a maximum power dissipation of 6 W, the 125 g module supports field cable runs up to 1000 m shielded or 600 m unshielded.

Hardware Specifications

Parameter Specification
Model DC 732F (3BDH000375R0005)
Base Model DC 732F
Brand ABB
Origin Sweden
Weight 125 g
Dimensions 67.5 mm x 54 mm x 76 mm (W x H x D)
Operating Temp -20 deg C to +60 deg C
Power Consumption 6 W max power dissipation (0.15 A at 24 VDC external)
Number of Channels 32 channels
Signal Type Digital Input/Output
Input Voltage Range "0" -30 V to +5 V
Input Voltage Range "1" +13 V to +30 V
Common Mode Voltage 24 VDC
Max Field Cable Length 1000 m (shielded), 600 m (unshielded)
Mechanical Form Factor S700 module housing
Status Diagnostics 40 front LEDs for signal status and error indication

Backplane Bus Communication Velocity and Firmware Flash Compatibility

The digital module interfaces directly with the S700 backplane bus to ensure rapid backplane bus communication velocity during full 32-channel scan updates. High-density discrete routing enables high I/O density scaling within space-constrained cabinets without increasing local bus latency. Controller firmware flash compatibility allows online parameter loading and diagnostic configuration changes directly across the backplane interface, maintaining synchronization between field status registers and the main CPU loop.

Frequently Asked Questions

Q: How do the front status LEDs indicate signal states across the digital channels?

A: A yellow LED is dedicated to each individual channel, illuminating continuously whenever the corresponding input or output channel registers a high signal state (signal 1).

Q: What are the cable length limits for shielded versus unshielded field wiring connections?

A: Shielded field cables may extend up to 1000 m in length, while unshielded field wiring must not exceed 600 m to prevent excessive signal attenuation and noise interference.

Field Installation Guidelines

  • Lock the module onto the corresponding S700 terminal base unit until the mechanical mounting clips firmly snap in place.
  • Verify that the external 24 VDC power supply circuit is de-energized before connecting power terminal wires.
  • Route field input and output wiring away from high-voltage AC conductors to minimize electromagnetic noise coupling.
  • Connect shielded cable braids directly to the enclosure ground terminal bar using low-impedance grounding clamps.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Understanding Safety Relays in Industrial Automation: Architecture, Operation, and Functional Safety

Standard electromechanical relays provide basic electrical isolation between low-voltage control circuits and high-power output loads. A traditional switching relay features a magnetic coil driving mechanical Common (COM), Normally-Open (NO), and Normally-Closed (NC) contacts. However, standard relays pose severe functional risks when deployed in critical safety interlock circuits. High current inrush or mechanical wear can weld contacts together permanently. If contact welding occurs in an emergency stop circuit, pressing the button fails to halt hazardous machinery movements. Consequently, global functional safety standards prohibit standard relays for critical machine guarding functions.

Read more
Mastering Wire Identification in Industrial Automation: The Power of Ferrules and Cross-Ferruling

Mastering Wire Identification in Industrial Automation: The Power of Ferrules and Cross-Ferruling

Proper wire labeling forms the cornerstone of reliable control system installation and long-term maintenance. In complex industrial automation environments, technicians terminate thousands of conductor ends inside control panels, marshalling racks, and field junction boxes. Ferrules serve as individual tube-shaped sleeve markers slipped onto conductors before final termination. While technicians historically relied on pre-printed individual letter rings, modern control panel builders utilize automated ferrule printing machines. These thermal-transfer printers generate durable, single-sleeve heat-shrink tags directly matching approved wiring schematics, significantly accelerating cabinet assembly workflows.

Read more
Understanding Marshalling Cabinets in Industrial Automation and Control Systems

Understanding Marshalling Cabinets in Industrial Automation and Control Systems

Marshalling cabinets serve as the crucial connection hub between field instruments and centralized processing units. In large DCS and PLC control system architectures, hundreds of multipair field cables run from local junction boxes to the central instrument equipment room. The marshalling cabinet houses field terminal blocks, surge arresters, intrinsic safety isolation barriers, and interposing relays. By segregating field field-wiring terminations from sensitive processor hardware, engineers protect expensive controller backplanes from high-voltage transients. Consequently, this modular separation dramatically streamlines maintenance workflows and simplifies system expansion.

Read more