Only 10 left - Selling fast

PRODUCT SKU : 1734-IB8

PRODUCT TYPE : Digital Input Module

PRODUCT VENDOR : Allen-Bradley


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Description

The Allen Bradley 1734-IB8 is a POINT I/O digital input module designed for distributed control systems requiring compact, modular input solutions. It provides eight sinking DC input channels with user-selectable filtering, making it suitable for high-speed and noise-sensitive applications. The module integrates seamlessly into POINT I/O systems, offering efficient power usage and clear diagnostic indicators.

Technical Specifications

  • Manufacturer: Allen Bradley

  • Product Line: POINT I/O 1734

  • Category: PLC Input Modules

  • Model / Part Number: 1734-IB8

  • Weight: 0.13 lbs (0.06 kg)

  • Module Type: Digital DC sinking input

  • Number of Inputs: 8 channels

  • Input Voltage Range: 10–28.8 VDC

  • Nominal Input Voltage: 24 VDC

  • Input Current Range: 2–5 mA

  • Nominal Input Current: 4 mA @ 24 VDC

  • Maximum Input Current: 5 mA

  • Input Filter Time: 0.5 ms hardware + 0–63 ms user-configurable

  • Power Dissipation: 1.6 W / 5.5 BTU per hour

  • POINTBus Current Draw: 75 mA

  • Enclosure Type: Open-style (no protective housing)

  • Keyswitch Position: 1

  • Module Location: Compatible with 1734-TB or 1734-TBS wiring base assemblies

  • Status Indicators:

    • 1 green/red LED (logic side, module status)

    • 8 yellow LEDs (logic side, input status)

Application Scenarios

The 1734-IB8 is widely used in distributed I/O systems for monitoring sensors, switches, and other DC input devices. Its compact design and modular wiring base compatibility make it ideal for applications requiring scalable input expansion.

FAQ

Q: How many inputs does this module provide?  A: It supports eight sinking DC input channels.

Q: What is the nominal input voltage?  A: The module is designed for 24 VDC nominal input, with a range of 10–28.8 VDC.

Q: Can the input filter time be adjusted?  A: Yes, it includes a hardware filter of 0.5 ms plus a user-selectable range of 0–63 ms.

Q: What wiring bases are compatible?  A: It can be installed on 1734-TB or 1734-TBS base assemblies.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Navigating Industrial Automation Failures: Types, Causes, and Mitigation Strategies

Modern manufacturing relies heavily on automated control systems to maximize throughput and maintain product quality. However, unplanned downtime in industrial automation can cost facility operators thousands of dollars per hour. Understanding how programmable logic controllers (PLCs), distributed control systems (DCS), and field instrumentation fail empowers engineering teams to implement robust preventive maintenance strategies.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

The Role of Intrinsic Safety Barriers in PLC and DCS Architectures

Implementing robust protection in hazardous industrial environments represents a fundamental safety requirement in factory automation. Process facilities often handle volatile gases, dusts, and chemical agents that pose significant combustion risks. Consequently, control system engineers must deploy energy-limiting interfaces to isolate safe-area control cabinets from hazardous-area field instrumentation. This article examines the function, selection, and electrical principles of intrinsic safety barriers within modern PLC and DCS networks.

Read more