PRODUCT SKU : 9907-029

PRODUCT TYPE : Synchronizer Modules

PRODUCT VENDOR : Woodward


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for precision generator paralleling, the Woodward 9907-029 (SPM-A Synchronizer Module) provides direct electrical execution of frequency, phase angle, and voltage matching within turbine and engine control systems.

Hardware Specifications

Parameter Specification
Model 9907-029
Brand Woodward
Origin Not specified
Weight 5.88 lbs
Power Consumption 5 W
Input Voltage 115 to 230 VAC (+/- 10%)
Frequency Range 50 to 60 Hz

Actuator Loop Feedback Response and Load Management

The 9907-029 synchronizer governs parallel power generation by providing dynamic bias signals to speed controllers. The module manages actuator loop feedback response through field-adjustable dynamic settings, which must be tuned relative to the inertia of the prime mover; small engines typically require high-response settings, while large-scale gas or steam turbines necessitate damped, slower dynamic parameters. The unit incorporates precise voltage matching capabilities capable of 1% accuracy and maintains a phase angle lock within +/- 10 degrees. The dual-impedance output architecture ensures compatibility with diverse load-sharing interfaces, including high-impedance 2301 and low-impedance 2301A/EPG/2500 control platforms.

Frequently Asked Questions

Q: How should the dynamic settings be adjusted for a large-scale steam turbine application?

A: For large-scale turbomachinery, dynamic response settings must be configured to a slower rate to prevent control loop instability and potential over-correction during synchronization.

Q: Is the 9907-029 compatible with both 115 VAC and 230 VAC bus sensing inputs?

A: Yes. The module is engineered for universal input voltage operation within the 115 to 230 VAC range (with a +/- 10% tolerance), making it suitable for standard utility grid or isolated bus sensing.

Field Installation Guidelines

  • Mounting: Install the module in a vibration-shielded control cabinet environment. Ensure all terminal connections are secured to prevent signal drift in the speed bias circuits.
  • Wiring: Utilize shielded twisted-pair wiring for all speed bias output signals. Terminate shields at the control system ground to avoid ground loop currents that could affect phase-matching accuracy.
  • Interface Selection: Select the appropriate output impedance (high or low) based on the specific load-sharing controller (e.g., 2301 vs. 2301A/EPG) to ensure signal impedance matching.
  • Calibration: Perform a bus frequency and phase-matching verification using a reference synchronoscope before initial unit paralleling to ensure the 1% voltage matching capability is calibrated correctly for the application.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why 24V DC Power Supplies Standardize Modern Industrial Automation

Why 24V DC Power Supplies Standardize Modern Industrial Automation

Industrial control cabinets worldwide rely on 24V DC as the universal power standard for field instrumentation, sensors, and controllers. Walk into any manufacturing plant, and you will find PLCs, human-machine interfaces (HMIs), and smart actuators running on extra-low voltage DC. Standardizing on 24V DC enhances operational safety, lowers cabinet footprint, and maintains steady control performance across factory networks.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
Mastering Modern Industrial Joystick Controls in Heavy Automation

Mastering Modern Industrial Joystick Controls in Heavy Automation

Industrial joysticks play a pivotal role in human-machine interaction across heavy material handling and mobile hydraulics. These tactile controllers translate complex operator movements into precise electrical signals for PLCs, motion controllers, and DCS networks. Consequently, selecting and installing the right joystick architecture ensures operator safety, reduces fatigue, and optimizes equipment performance.

Read more