Product Details

Product Overview

The 1747-L514 is a foundational modular processor within the Allen-Bradley SLC 500 family, specifically designated as an SLC 5/01 controller. Engineered for entry-level to mid-range industrial automation tasks, the 1747-L514 (PN: 1747-L514) provides a reliable execution environment for discrete and analog control. It resides exclusively in Slot 0 of an SLC 500 chassis and supports DH-485 communication for networked data exchange and programming.

Technical Specifications

  • Manufacturer Allen-Bradley / Rockwell Automation

  • Product Line SLC 500 Modular Hardware

  • Model Number 1747-L514

  • Processor Type SLC 5/01

  • User Program Memory 4K Instructions (approx. 4,000 words)

  • Memory Storage Capacitor-backed RAM (Internal)

  • Non-Volatile Backup Compatible with 1747-M1 (1K) and 1747-M2 (4K) EEPROM modules

  • EEPROM Adapter Socket 1747-M5

  • Maximum I/O Capacity 960 Discrete I/O points

  • Analog I/O Capacity 480 points

  • Chassis Expansion Supports up to 3 interconnected chassis

  • Max Module Count 30 local I/O modules

  • Typical Program Scan Time 8 milliseconds per 1K

  • I/O Scan Time 2.6 milliseconds

  • Communication Interface DH-485 (RJ-45 port)

  • Backplane Current (5V DC) 350 mA

  • Backplane Current (24V DC) 105 mA

  • Operating Temperature 32-140°F (0-60°C)

  • Shipping Weight 0.75 lbs (0.34 kg)

Supported Instruction Sets

The 1747-L514 utilizes a robust instruction set suitable for standard logic and mathematical operations, including:

  • Bit-level logic (XIC, XIO, OTE, etc.)

  • Timer and Counter instructions (TON, TOF, RTO, CTU, CTD)

  • Comparison operations (EQU, NEQ, LES, GRT)

  • Basic Math (ADD, SUB, MUL, DIV)

  • Data Handling (Move, Copy, Bit Shift)

  • Program Flow Control (Jump, Subroutine, MCR)

  • Sequencer instructions for automated step-based logic

Frequently Asked Questions

  • How long will the capacitor-backed RAM hold the program without power?

    The internal capacitor of the 1747-L514 is designed to retain memory for short periods (typically several days to a few weeks depending on ambient temperature). For long-term storage, a 1747-M1 or 1747-M2 EEPROM is required.

  • Does the 1747-L514 support EtherNet/IP or ControlNet?

    Native support is limited to DH-485. Connecting to Ethernet would require an external bridge such as a 1761-NET-ENI or upgrading to a higher-tier SLC processor like the 5/05.

  • Can this processor be placed in any slot?

    No, the 1747-L514 must always be installed in Slot 0 (the leftmost slot) of the primary local chassis.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Will PLCs Become Obsolete? The Future of PLC Controllers in Industrial Automation

Will PLCs Become Obsolete? The Future of PLC Controllers in Industrial Automation

PLCs remain a core technology in industrial automation, controlling machines, production lines, and process equipment. Although AI, machine learning, and Industrial IoT are transforming smart manufacturing, PLC hardware still plays a critical role in executing real-time control tasks and ensuring reliable operation in modern factory automation systems.

Read more
Open Platform Communications (OPC) in Industrial Automation: Enabling Data Exchange Between PLC, DCS, and Control Systems

Open Platform Communications (OPC) in Industrial Automation: Enabling Data Exchange Between PLC, DCS, and Control Systems

Open Platform Communications (OPC) is a key communication standard in modern industrial automation. It enables reliable data exchange between devices from different manufacturers. By providing a common interface, OPC allows PLC, DCS, SCADA, and HMI systems to share real-time process data, improving system integration, efficiency, and control across industrial environments.

Read more
Siemens PLC Memory Structure: Understanding Load, Working, System, and Retentive Memory in Industrial Automation

Siemens PLC Memory Structure: Understanding Load, Working, System, and Retentive Memory in Industrial Automation

Programmable logic controllers (PLCs) use structured memory to store programs, process data, and system variables in industrial automation systems. This article explains the Siemens PLC memory architecture, including load memory, working memory, system memory, and retentive memory, and how these components support reliable control, efficient factory automation, and stable DCS operations.

Read more