PRODUCT SKU : ATV320U04N4B

PRODUCT TYPE : Variable Speed Drive

PRODUCT VENDOR : Schneider


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Overview
The ATV320U04N4B from Schneider is a compact variable speed drive from the Altivar Machine ATV320 series, designed for precision control of complex machines. Rated at 0.37 kW (0.5 HP), it supports 3-phase 380–500 V supply with integrated EMC Class C2 filtering and IP20 protection. Its cabinet-mount format, advanced motor control profiles, and multiple communication options make it suitable for versatile industrial applications.

Motor Control

  • Quadrant Operation: 4-quadrant control for forward/reverse and braking

  • Motor Profiles: Asynchronous V/f, flux vector without sensor, energy-saving modes; synchronous vector control without sensor

  • Maximum Output Frequency: 599 Hz

  • Acceleration/Deceleration: Linear, ramp-adaptive, with DC injection braking

  • Switching Frequency: Adjustable 2–16 kHz (nominal 4 kHz)

  • Brake Chopper: Integrated

Electrical Specifications

  • Rated Supply Voltage: 380–500 V (–15…+10 %)

  • Nominal Output Current: 1.5 A

  • Line Current: 2.1 A @ 380 V, 1.6 A @ 500 V

  • Apparent Power: 1.4 kVA @ 500 V

  • Transient Overtorque: 170–200 % of nominal motor torque

Inputs & Outputs

  • Discrete Inputs: 7 (STO, logic, and pulse inputs up to 30 kHz)

  • Discrete Outputs: 3 (open collector, 0–1 kHz, 30 V DC, 100 mA)

  • Analog Inputs: 3 (AI1 0–10 V, AI2 ±10 V, AI3 0–20 mA configurable)

  • Analog Output: 1 (configurable 0–20 mA / 0–10 V)

  • Relay Outputs: Configurable R1A/B/C, R2A/C up to 100,000 cycles

  • Protection: Input phase loss, output overcurrent, overheating, short-circuit, thermal

Communication

  • Protocols: Modbus, CANopen; optional cards for EtherCAT, PROFINET, Profibus DP V1, DeviceNet, Ethernet Powerlink, EtherNet/IP

  • Ports: Modbus serial, CANopen

Mechanical & Environmental

  • Dimensions (W×H×D): 45 × 325 × 245 mm

  • Weight: 2.5 kg

  • Mounting: Vertical ±10°

  • IP Rating: IP20

  • Operating Temperature: –10…50 °C (without derating), 50–60 °C (with derating)

  • Storage Temperature: –25…70 °C

  • Humidity: Class 3K5 (IEC 60721-3)

  • Shock/Vibration: 150 m/s² (11 ms), 10 m/s² (13–200 Hz)

  • Cooling Air Volume: 9.4 m³/h

  • Overvoltage Category: III

  • Regulation Loop: Adjustable PID

  • Speed Accuracy: ±10 % of nominal slip

  • Pollution Degree: 2

Applications

  • Precision motor control for pumps, conveyors, fans, and machinery

  • Energy-efficient speed regulation and torque adaptation

  • Integration into Modbus or CANopen automation networks for industrial equipment

FAQ

Q1: What is the rated motor power of ATV320U04N4B?
A1: 0.37 kW (0.5 HP), suitable for small-to-medium complex machines.

Q2: Which communication protocols are supported?
A2: Modbus and CANopen; optional cards add EtherCAT, PROFINET, Profibus DP, DeviceNet, and Ethernet Powerlink.

Q3: Can it operate in hot environments?
A3: Yes, up to 50 °C without derating; 50–60 °C with current derating.

Q4: What is the maximum switching frequency?
A4: Adjustable from 2 to 16 kHz, nominal at 4 kHz.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding VFD Mechanical Brake Logic and Control in Industrial Automation

Understanding VFD Mechanical Brake Logic and Control in Industrial Automation

Variable Frequency Drives (VFDs) play a crucial role in modern industrial automation by controlling motor speed, torque, and acceleration. However, high-inertia loads and vertical lifting systems require precise mechanical braking logic to ensure operational safety and prevent equipment damage.

Read more
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more