Skip to content

What are you looking for?


You may also like

Honeywell 2MLF-AD8A MasterLogic-200 Analog Input ModuleHoneywell 2MLF-AD8A MasterLogic-200 Analog Input ModuleHoneywell 2MLF-AD8A MasterLogic-200 Analog Input Module
Honeywell 2MLF-AD8A MasterLogic-200 Analog Input Module
Honeywell 2MLF-AD8A MasterLogic-200 Analog Input Module
Honeywell 2MLF-AD8A MasterLogic-200 Analog Input Module

Honeywell 2MLF-AD8A MasterLogic-200 Analog Input Module


Only 10 left - Selling fast

PRODUCT SKU : 2MLF-AD8A

PRODUCT TYPE : Analog Input Modules

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Honeywell 2MLF-AD8A, also cataloged as the 2MLF-AD8A Analog Input Module, operates as a dedicated hardware component for high-speed voltage and current signal acquisition within MasterLogic-200 PLC networks.

Hardware Specifications

Parameter Specification
Model 2MLF-AD8A
Brand Honeywell
Origin South Korea
Weight Approx. 0.1 kg
Dimensions 426 mm x 98 mm x 19 mm
Operating Temp 0 to 55 deg C
Power Consumption <= 100 mA at 24 VDC (+/-10%)
Input Channels 8 analog inputs
Input Ranges Voltage: +/-10 V, 0-10 V, 0-5 V; Current: 0-20 mA, 4-20 mA
Resolution 12-bit
Conversion Speed 1 ms / channel
Input Impedance Voltage: >= 2 Mohm; Current: <= 250 ohm
Isolation Photo-coupler isolation between channels and system logic
Connection Type 40-pin connector
Recommended Cable Size 0.3 mm2

Process Control Signal Isolation and Field Instrumentation Protocol

The 2MLF-AD8A module provides high-speed analog-to-digital processing across 8 selectable voltage or current input channels. Designed to interface with standard process instruments such as 4-20 mA HART loop protocol transmitters and +/-10 V sensors, the onboard circuitry utilizes photo-coupler isolation between field wiring terminals and the central backplane bus. An input impedance profile of >= 2 Mohm on voltage ranges and <= 250 ohm on current loops prevents signal attenuation and voltage drops, maintaining precise 12-bit conversion integrity at a hardware throughput rate of 1 ms per channel.

Frequently Asked Questions

Q: What input signal ranges can be configured on individual channels of the 2MLF-AD8A?

A: Each channel accepts standard voltage ranges (+/-10 V, 0-10 V, 0-5 V) or current ranges (0-20 mA, 4-20 mA) configured through system software.

Q: How is field ground noise isolated from the MasterLogic-200 backplane?

A: Electrical noise and common-mode surge voltages are blocked via photo-coupler isolation layers located between field input channels and internal PLC system logic.

Q: What external supply voltage is required to power the analog processing circuitry?

A: The module requires an external power supply of 24 VDC (+/-10%) drawing <= 100 mA of current.

Field Installation Guidelines

  1. Turn off backplane rack power and external 24 VDC loop power before inserting or removing the 2MLF-AD8A module from the chassis slot.
  2. Terminate all incoming 4-20 mA or voltage sensor wires to the designated 40-pin connector using wire sizes rated at 0.3 mm2.
  3. Use shielded twisted-pair cabling for all analog input signal lines to minimize industrial electromagnetic noise coupling.
  4. Ground cable shields at a single panel ground point near the cabinet entrance, avoiding dual-ended grounding to prevent ground loop currents across non-isolated channel commons.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Comprehensive Guide to Servo Motor Drive Control Techniques in Industrial Automation

Comprehensive Guide to Servo Motor Drive Control Techniques in Industrial Automation

Precision motion control systems drive high-throughput manufacturing across modern industrial automation environments. Unlike standard induction motors running on basic variable frequency drives, servo motor systems deliver sub-millimeter positioning accuracy and fast dynamic response.

Read more
Industrial PLC Communication Protocols: A Comprehensive Engineering Guide

Industrial PLC Communication Protocols: A Comprehensive Engineering Guide

Modern factory automation relies heavily on industrial communication protocols to connect field instruments, controllers, and enterprise networks. Beyond traditional hardwired I/O, robust communication networks allow programmable logic controllers (PLCs) to exchange telemetry, diagnostic data, and control commands efficiently across complex architectures.

Read more
Understanding PLC Digital Output Types: Relay, Transistor, and Triac Explained

Understanding PLC Digital Output Types: Relay, Transistor, and Triac Explained

Programmable Logic Controllers (PLCs) form the backbone of modern industrial automation systems. They interface directly with field devices such as solenoid valves, indicator lights, motor starters, and interposing relays. Selecting the correct digital output module ensures high system availability and long hardware service life.

Read more