Product Details
The 3500/32-01-00 (composed of part numbers 149986-02 and 125720-02) is a full-height 4-channel relay output module designed for the Bently Nevada 3500 Machinery Protection System. It provides four independent relay channels that can be programmed to actuate based on alert, danger, or NOT-OK status conditions from any monitor module in the rack, supporting machinery safety shutdown and alarm annunciation workflows.
Functional Configuration and Logic
Each of the four relay channels can be independently configured using the 3500 Rack Configuration Software to execute custom voting logic utilizing AND/OR combinations. Input sources can map directly to alarm conditions, channel statuses, or Proportional-Plus-Local (PPL) variables across the rack framework.
The module features switch-selectable operation modes for each channel, allowing technicians to set relays as either Normally Energized or Normally De-energized depending on failsafe system design requirements. An integrated arc suppressor is installed as standard to extend contact longevity under inductive load switching.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | 3500/32-01-00 |
| Brand | Bently Nevada |
| Module Composition | 149986-02 (Relay Control Module) + 125720-02 (Relay Output Module) |
| Relay Type | Single-pole, double-throw (SPDT), epoxy-sealed |
| Power Consumption | 5.8 W typical |
| Contact Life | 100,000 cycles at 5 A, 24 Vdc or 240 Vac |
| DC Resistive Load Rating | Max 2 A (0 to 30 Vdc), 0.75 A (48 Vdc), 0.2 A (125 Vdc) |
| AC Resistive Load Rating | Max 250 Vac, 2 A, max switched power 450 VA |
| Operating Temperature | -30 deg C to +65 deg C (-22 deg F to +150 deg F) |
| Storage Temperature | -40 deg C to +85 deg C (-40 deg F to +185 deg F) |
| Humidity | 95%, non-condensing |
| Main Module Dimensions | 241 mm x 24.4 mm x 242 mm (9.50 in x 0.96 in x 9.52 in) |
| Main Module Weight | 0.7 kg (1.6 lb) |
| Country of Origin | United States |
Installation and Compatibility
The main module occupies one full-height front slot, while its matching I/O module occupies one full-height rear slot in any available slot to the right of the Transient Data Interface (TDI) module. The unit requires 3500 Rack Configuration Software version 4.5 or later for proper setup and parameter flashing.
For hazardous area or functional safety installations, field wiring voltages must comply strictly with certified limits (such as max 30 Vdc/Vac) to maintain safety ratings and prevent certification invalidation.
Frequently Asked Questions
Q: Can the Rack OK relay output on this module be utilized for auto-shutdown protection circuits?
A: No. The Rack OK relay should be restricted to general annunciation purposes only, as dozens of internal event conditions can trigger a NOT-OK status.
Q: What software is required to configure the relay voting logic for this module?
A: Configuration requires the Bently Nevada 3500 Rack Configuration Software (version 4.5 or later) connected via the TDI front USB port or network interface.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.