Configured for ultraviolet radiation detection and fast response signal generation in gas turbine flame monitoring systems, the Honeywell LG1093AA44 (LG1093 Flame Sensor) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model LG1093AA44
Brand Honeywell
Origin USA
Weight 3.0 kg (Shipping Weight)
Dimensions 3/4 inch internal NPT mounting / 1 inch external conduit thread
Operating Temp -40 deg C to +176 deg C
Power Consumption Sensor head contains no active power supply (Passive GM tube)
Spectral Range 180 nm to 260 nm (Ultraviolet spectrum)
Pressure Rating Viewing window rated for 10 bar (150 psi)
Cable Assembly Integral Teflon-shielded cable, 16 ft (4.9 m) length
Flame Response Time Flame Present: 0.1 sec typical; Flame Loss: 0.2 sec max
Signal Output Compatible with EG1033 series amplifier modules
Transmission Distance Up to 330 m (1,000 ft) sensor-to-amplifier distance
Hazardous Approvals ATEX (EEx d IIA T3 / EEx d IIC T3, Zone 1 & 2), FM (Class I, Div 1 & 2, Groups B, C, D)

4-20 mA HART Loop Protocol and Channel-to-Channel Isolation

The optical sensor assembly utilizes a solar-blind Geiger Mueller phototube engineered to isolate ultraviolet radiation signals in the 180 nm to 260 nm spectral band while ignoring infrared and black-body radiation background noise. Electrical channel-to-channel isolation between the optical sensing head and the associated EG1033 amplifier module prevents ground loop currents across the 330 m transmission line. This isolation structure preserves pulse frequency fidelity during high-speed signal processing and emergency trip execution within turbine control architectures.

Frequently Asked Questions

Q: What amplifier modules are compatible with the LG1093AA44 flame sensor?

A: The sensor operates specifically with Honeywell EG1033 series amplifier modules (including EG1033AA transistor open-collector outputs, and EG1033AB or EG1033AC SPDT relay contact outputs).

Q: Can the LG1093AA44 be installed on Dry Low NOx (DLE) gas turbines?

A: No, standard LG1093 series sensors are not optimized for low-emissions combustors; DLE gas turbine applications require pre-selected sensor variants tailored for low UV intensity flames.

Q: What is the maximum pressure limit for the optical viewing window?

A: The integrated optical viewing window is rated to withstand turbine sight-pipe combustion pressures up to 10 bar (150 psi).

Field Installation Guidelines

  • Thread the sensor body onto the 3/4 inch NPT sight pipe connection, ensuring a minimum of 5 full NPT thread engagements with high-temperature pipe sealant.
  • Pass the integral 16 ft Teflon-shielded cable through a 1 inch protective metal conduit to safeguard against physical abrasion and radiant heat.
  • Ground the cable shield drain wire strictly at the EG1033 amplifier terminal strip to eliminate circulating chassis ground loops.
  • Inspect and clean the sight glass window periodically using a non-abrasive solvent wipe to prevent soot buildup from attenuating UV light transmission.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more