Product Details

The Emerson CON041-CN+PR6423/000-031, also cataloged as the CON041-CN / PR6423 Proximity Sensors, operates as a dedicated hardware component for non-contact shaft vibration, position, and eccentricity measurement within Emerson MMS 6000 and MMS 3000 platforms. The hardware system links an 8 mm inductive proximity probe with the CON041-CN signal converter module to evaluate spatial displacement against conductive ferromagnetic targets. High-frequency oscillator fields convert dynamic surface gap deviations directly into linear continuous voltage or current signals without physical mechanical wear.

Hardware Specifications

Parameter Specification
Model CON041-CN+PR6423/000-031
Brand Emerson
Origin United States
Operating Temp -35 to +180 deg C (Sensor) / -35 to +150 deg C (Cable)
Power Consumption Standard loop power (24 VDC supply)
Supply Voltage 24 VDC
Measurement Range Typically +/-2 mm peak-to-peak; linear up to 4 mm
Sensitivity 8 V/mm (203.2 mV/mil) +/-5%
Frequency Range 0 to 20000 Hz (-3 dB)
Output Signal Analog voltage (0-10 V) or current (4-20 mA)
Target Material Ferromagnetic steel (e.g., 42CrMo4)
Ingress Protection IP65

4-20 mA HART Loop Protocol & Channel Isolation

The CON041-CN signal converter incorporates high-speed conditioning circuitry with a < 15 us rise time to support broad dynamic frequency ranges up to 20000 Hz. The signal path provides continuous channel-to-channel isolation to prevent potential differences between adjacent sensor loops from introducing noise into process monitoring circuits. Configured for standardized 4-20 mA HART loop protocol signaling alongside direct voltage modes, the driver compensates for thermal variations across the -35 to +180 deg C range to maintain exact scale factor linearity.

Frequently Asked Questions

Q: How is the CON041-CN converter secured in control cabinets?

A: The converter module utilizes a standardized DIN rail mounting chassis for direct snap-on installation within industrial control enclosure racks.

Q: What target surface material is required for the PR6423 sensor calibration?

A: The sensor sensitivity of 8 V/mm is factory-calibrated for ferromagnetic steel targets, such as 42CrMo4 steel shafts.

Field Installation Guidelines

Maintain an unobstructed lateral clearance zone around the 8 mm probe tip equal to at least 1.5 times the tip diameter to eliminate uncalibrated side-wall interference from metallic surroundings. Mount the CON041-CN converter securely onto a standard DIN rail inside a protective enclosure. Route sensor extension leads through dedicated grounded metallic conduit, keeping signal paths physically separated from high-voltage AC feeds or motor drive connections. Connect all cable shields to technical functional earth at a single point only to prevent circulating ground currents.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Manufacturing Execution Systems serve as the digital backbone of modern factory floors. Positioned at Level 3 of the ISA-95 automation pyramid, MES links enterprise resource planning with real-time shop floor control systems. Today, industrial operators rely on MES software to bridge operational strategy with physical production execution.

Read more
Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Industrial Ethernet forms the backbone of factory automation. Selecting the right switch architecture determines system uptime, data throughput, and OT cyber resilience. This technical guide evaluates managed vs. unmanaged switches, analyzing operational differences, security controls, and selection criteria.
Read more
Hot Standby vs. Cold Standby Redundancy in Industrial Automation

Hot Standby vs. Cold Standby Redundancy in Industrial Automation

System availability determines process safety and productivity in industrial automation. Control engineers deploy redundancy to eliminate single points of failure. This technical guide evaluates Hot Standby vs. Cold Standby architectures, comparing failover speeds, memory sync, cost trade-offs, and field selection criteria.

Read more