Product Details

Configured for non-contacting shaft displacement tracking in turbomachinery protection systems, the Emerson CON021+PR6424/003-010 (CON021+PR6424/003-010 Proximity Sensors) provides direct physical/electrical execution. The paired assembly maps physical micro-displacements directly into linear voltage output variations, routing dynamic vibration signals to downstream machinery monitoring instrumentation.

Hardware Specifications

Parameter Specification
Model CON021+PR6424/003-010
Brand Emerson
Origin Germany
Weight 0.58 kg
Dimensions 24 cm x 23 cm x 4 cm
Operating Temp Sensor: -35 to +150 deg C, Converter: -30 to +100 deg C
Power Consumption System loop powered via negative supply rail
Input Voltage Range -23 V to -32 V DC primary supply input
Output Voltage Range -4 V to -20 V DC standard operational range
Measurement Range +/- 2.0 mm dynamic displacement span
Nominal Sensitivity 4 V/mm (101.6 mV/mil)
Frequency Range 0 to 20000 Hz continuous tracking (-3 dB attenuation point)
Signal Response Time Less than 15 us transient step delay
Pressure Resistance Up to 10000 hPa (145 psi) at the sensor head
Target Material Profile Ferromagnetic steel
Protection Class IP20 certified converter chassis
Hazardous Certifications ATEX, IEC-Ex, CSA certified for hazardous area deployments

4-20 mA HART Loop Protocol and Channel Isolation

The CON021 signal converter provides channel-to-channel isolation across monitoring channels to prevent ground potential loops from degrading high-frequency signal integrity. When deployed in process monitoring environments incorporating 4-20 mA HART loop protocol networks and FOUNDATION Fieldbus segments, the analog measurement loop remains decoupled from switching noise and transient line interference. Integrated temperature stabilization maintains cold junction compensation reference integrity and precise output scaling over the entire operating temperature span.

Frequently Asked Questions

Q: What specific hardware behaviors manifest if a field wire becomes disconnected from the CON021 converter terminal block?

A: An open circuit on the sensor loop breaks the primary inductive bridge, causing the internal conditioning circuit to drive the output voltage to its maximum negative rail limit and trigger a channel fault alert on the host monitoring system.

Q: Can the PR6424/003-010 sensor head withstand high-pressure fluids if deployed directly inside a gearbox enclosure?

A: Yes, the sensor head features structural sealing that provides mechanical pressure resistance up to 10000 hPa (145 psi) to prevent fluid ingress into the internal coil assembly.

Q: What is the target static gap voltage for initial physical installation alignment?

A: Mechanical alignment is typically adjusted until the static gap voltage output measures -10 VDC, positioning the probe tip at the center of its linear dynamic range.

Field Installation Guidelines

  1. Mount the PR6424 probe securely into the bearing housing thread adapter, maintaining perpendicular alignment with the target shaft.
  2. Adjust mechanical insertion depth using a feeler gauge or by monitoring the static gap voltage until the converter output reads -10 VDC.
  3. Lock the probe body into position using the external retaining locknut, ensuring torque limits do not deform the mounting sleeve.
  4. Mount the CON021 converter on a standard DIN rail inside an IP-rated enclosure, respecting ambient temperature limits of -30 to +100 deg C.
  5. Connect extension cable shields to dedicated isolation terminals, ensuring cable shields are grounded at the monitoring cabinet end only.
  6. Verify primary supply voltage (-23 V to -32 V DC) at the converter power terminals prior to commissioning the monitoring channel.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more