Product Details

Configured for high-speed network communication and serial interface processing in Honeywell Safety Manager platforms, the Honeywell FC-USI-0002 CC V2.0 (FC-USI-0002 Universal System Interface Module) provides direct physical/electrical execution.

Suffix Breakdown & Model Matrix

Model Number Revision / Coating Communication Ports Operating Temperature
FC-USI-0002 CC V2.0 Conformal Coated (CC), Rev V2.0 2x Ethernet, 2x Serial (RS-232/485) -20 to +50 deg C
FC-USI-0002 CC V1.0 Conformal Coated (CC), Rev V1.0 2x Ethernet, 2x Serial (RS-232/485) -20 to +50 deg C

Hardware Specifications

Parameter Specification
Model FC-USI-0002 CC V2.0
Brand Honeywell
Origin USA
Weight 0.8 kg
Dimensions 105 mm x 105 mm x 29 mm
Operating Temp -20 to +50 deg C
Power Consumption Max 1.2 A at 24 VDC / 5 VDC +/-5%
Ethernet Ports 2 ports (10/100 Mbps)
Serial Channels 2 channels (RS-232 / RS-485)
Flash Memory 8 MB
Local SRAM 8 MB with EDAC
Shared RAM 256 KB

Channel-to-Channel Isolation & Protocol Management

The FC-USI-0002 CC V2.0 features dual isolated serial channels (RS-232/RS-485) and dual 10/100 Mbps Ethernet ports engineered for high-availability process control networks. Integrated channel-to-channel isolation and galvanic shielding protect internal 256 KB Shared RAM buffers from field-side ground loops and surge transients. Compatible with 4-20 mA HART loop protocol gateways and DCS controllers, the unit preserves high-speed backplane data integrity without compromising safety processor determinism.

Frequently Asked Questions

Q: What is the primary difference between revision V2.0 and earlier hardware revisions of the FC-USI-0002 CC?

A: Revision V2.0 incorporates updated internal bus components and firmware flash compatibility enhancements while maintaining identical physical dimensions, power pinouts, and backplane slot compliance.

Q: How does the local memory error handling operate during active system operation?

A: The 8 MB local SRAM features built-in Error Detection and Correction (EDAC) hardware logic that automatically identifies and rectifies single-bit memory faults in real time.

Field Installation Guidelines

  1. Isolate all rack primary power feeds prior to inserting or removing the FC-USI-0002 CC V2.0 module from its backplane slot.
  2. Verify that serial communication links (RS-232/RS-485) utilize shielded twisted-pair cables with drain wires terminated to a single earth ground bar.
  3. Secure RJ45 network cabling using mechanical connector latches to prevent intermittent Ethernet communication drops.
  4. Maintain control cabinet environmental temperature within -20 to +50 deg C with relative humidity below 95% (non-condensing).

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more