Skip to content

What are you looking for?


You may also like

TK-IDD321 | Honeywell | Discrete Input ModuleTK-IDD321 | Honeywell | Discrete Input ModuleTK-IDD321 | Honeywell | Discrete Input Module
TK-IDD321 | Honeywell | Discrete Input Module
TK-IDD321 | Honeywell | Discrete Input Module
TK-IDD321 | Honeywell | Discrete Input Module

TK-IDD321 | Honeywell | Discrete Input Module


Only 10 left - Selling fast

PRODUCT SKU : TK-IDD321

PRODUCT TYPE : Digital I/O Cards

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Honeywell TK-IDD321, also cataloged as the TK-IDD321 Discrete Input Module, operates as a dedicated hardware component for sensing 24 VDC discrete field signals within Experion PKS C300 automation platforms.

Hardware Specifications

Parameter Specification
Model TK-IDD321
Brand Honeywell
Origin USA
Weight 0.24 kg (Shipping weight: 1.5 kg)
Dimensions Standard C300 / Experion I/O module profile
Operating Temp 0 to 60 deg C
Power Consumption 6.1 W maximum power dissipation
Number of Inputs 32 channels (16 points per common group)
Nominal Input Voltage 24 VDC
On-State Voltage Range 10 to 31.2 VDC @ 60 deg C (all channels)
On-State Current (Min) 2.0 mA
Off-State Voltage (Max) 5.0 VDC
Off-State Current (Max) 1.5 mA
Inrush Current Peak 250 mA peak (decaying to less than 37% in 22 ms)
Input Compatibility IEC 61131-2 Type 1+
Connection Terminal Block TC-TBCH 36-position terminal block

Channel-to-Channel Isolation & Signal Conditioning

In process automation networks, the module provides galvanic channel group isolation between incoming 24 VDC field contact circuits and the system backplane logic. The integrated filtering networks suppress high-frequency noise spikes and field switch contact chatter, maintaining signal integrity under noisy electrical conditions. Current-limiting circuitry on each input channel prevents internal card damage during continuous high-voltage input conditions, maintaining stable state detection across all 32 channels.

Frequently Asked Questions

Q: What type of switch contacts or proximity sensors can be interfaced with this input module?

A: The module interface complies with IEC 61131-2 Type 1+ input characteristics, making it compatible with standard dry contacts, 2-wire solid-state sensors, and 3-wire PNP proximity switches operating at 24 VDC.

Q: Are individual channels isolated from one another?

A: Channels are arranged into two groups of 16 points sharing a common return line per group, providing optical isolation between the field-side wiring group and the internal backplane system logic.

Q: How is field wiring terminated to the module assembly?

A: Field wiring connects directly via a removable 36-position TC-TBCH terminal block assembly, enabling module maintenance without disconnecting individual field wires.

Field Installation Guidelines

  1. Mount the module securely into its designated slot on the C300 I/O carrier assembly inside an IP54-rated industrial enclosure.
  2. Wire field signal lines to the 36-position TC-TBCH terminal block using stranded copper conductors compliant with local wire gauge standards.
  3. Observe polarity requirements for external 24 VDC sensor power supplies connected across the shared common points of each 16-channel group.
  4. Ground all shielded input cables at a single entry point on the enclosure cabinet earth ground bus bar to avoid ground potential loops.
  5. Maintain a minimum separation of 50 mm between 24 VDC signal wiring and high-voltage AC power lines within the enclosure trunking.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Redefining Control System Design: The Evolution of Flexible Input/Output Modules (FIOM) in Industrial Automation

Redefining Control System Design: The Evolution of Flexible Input/Output Modules (FIOM) in Industrial Automation

Traditional industrial automation relies heavily on dedicated input-output (IO) modules. In a standard distributed control system (DCS) or programmable logic controller (PLC) setup, design engineers assign specific cards to distinct signal types. For instance, a traditional 16-channel digital input (DI) card exclusively processes digital signals. However, engineering projects frequently encounter last-minute changes in signal counts. Therefore, discovering a missing analog input (AI) channel late in the design phase forces engineers to purchase and install an entirely new, dedicated AI card. Consequently, this rigidity drives up hardware expenses, wastes cabinet space, and delays commissioning schedules.

Read more
Mastering VFD Braking Theory and Mechanical Brake Sequencing in Industrial Automation

Mastering VFD Braking Theory and Mechanical Brake Sequencing in Industrial Automation

In industrial automation, variable frequency drives (VFDs) regulate motor speed and torque across manufacturing plants and material handling systems. However, certain heavy-duty applications experience external loads that can rotate the motor shaft without an active command. For instance, gravity pulls loads downward in unanchored hoisting equipment. Therefore, engineers integrate mechanical brakes with VFD logic to maintain absolute safety and prevent structural damage or personnel injury during shutdowns.

Read more
Optimizing Tank Level Control Using Proportional Algorithms in PLC Systems

Optimizing Tank Level Control Using Proportional Algorithms in PLC Systems

Industrial automation engineers frequently encounter liquid level regulation challenges across diverse process plants. Traditional ON-OFF control mechanisms often disrupt system stability due to abrupt actuator switching. Therefore, upgrading to closed-loop architectures like proportional control yields smoother responses. In a typical PLC environment, such as Siemens TIA Portal, engineers utilize closed-loop feedback to minimize process errors without requiring full PID complexity.

Read more