Product Details

The YOKOGAWA AAM21 S2, also cataloged as the AAM21 Analog Input Module, operates as a dedicated hardware component for dual-channel isolated analog voltage and current signal acquisition within YOKOGAWA CENTUM control systems.

Suffix Breakdown & Model Matrix

The catalog designation for the AAM21-S2 defines the base hardware architecture and revision parameters:

  • Base Model (AAM21): Analog Input Module architecture for voltage and current signal acquisition
  • Suffix ( S2): Hardware revision 2 designating standard nest mounting and interface parameter set

Hardware Specifications

Parameter Specification
Model AAM21 S2
Brand YOKOGAWA
Origin Japan
Operating Temp -10 to 55 deg C
Power Consumption 24 VDC (+/-10%)
Input Channels 2 channels (isolated)
Input Ranges 0 to 10 V, +/-10 V, 4 to 20 mA, 0 to 20 mA
Measurement Accuracy +/-0.1% of full scale
Resolution 16-bit
Sampling Rate 10 ms/ch (typical)
Isolation Voltage 1500 VAC channel-to-channel

Channel-to-Channel Isolation and 4-20 mA HART Loop Signal Acquisition

The AAM21-S2 provides 1500 VAC galvanic isolation between individual channels and internal backplane logic to prevent ground loop currents and suppress common-mode electrical noise. Operating at a 16-bit analog-to-digital conversion resolution with a 10 ms per channel sampling cycle, the module converts standard process signals—including 4-20 mA HART loop protocol field devices and +/-10 V transducers—into digital data frames for DCS backplane transmission.

Frequently Asked Questions

Q: What input signal ranges can be configured on the AAM21-S2 module?

A: The module accepts 0 to 10 V DC and +/-10 V DC voltage inputs, as well as 0 to 20 mA DC and 4 to 20 mA DC current inputs across its 2 isolated channels.

Q: What is the dielectric isolation rating between the individual input channels?

A: The module features channel-to-channel galvanic isolation rated at 1500 VAC to prevent cross-talk and signal distortion in noise-prone industrial environments.

Field Installation Guidelines

De-energize rack power prior to mounting or removing the AAM21-S2 module in the system I/O node slot. Observe electrostatic discharge (ESD) protection procedures, wearing a grounded wrist strap when handling the card. Align the module with guide rails and seat the rear connector firmly into the backplane socket, securing top and bottom retaining screws to establish frame ground continuity. Wire analog inputs using shielded twisted-pair cables, bonding the shield wire to earth ground at a single cabinet termination point to prevent ground loops. Maintain physical separation between low-voltage signal cables and AC power conductors.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Marshalling Cabinets in Industrial Control Systems Architecture

Understanding Marshalling Cabinets in Industrial Control Systems Architecture

Industrial control system deployments rely on structured signal distribution to bridge field instrumentation with central processing hardware. A marshalling cabinet serves as the vital intermediate connection point between heavy field home-run multi-pair cables and delicate input/output (I/O) modules housed inside Programmable Logic Controller (PLC) or Distributed Control System (DCS) enclosures. By segregating field cable terminations from control hardware, engineers maintain system flexibility, safeguard controller components, and streamline commissioning workflows.

Read more
FAT vs SAT in Industrial Control Systems: Key Differences and Execution Guide

FAT vs SAT in Industrial Control Systems: Key Differences and Execution Guide

Industrial control system deployment relies on strict verification protocols to guarantee operational safety, system stability, and regulatory compliance. Commissioning complex Programmable Logic Controller (PLC) racks, Distributed Control Systems (DCS), and Safety Instrumented Systems (SIS) requires two critical milestones: the Factory Acceptance Test (FAT) and the Site Acceptance Test (SAT). Both procedures validate that system automation meets design specifications, but they occur at different stages of project execution and target distinct operational risks.

Read more
Hub vs Switch vs Router in Industrial Automation Architecture

Hub vs Switch vs Router in Industrial Automation Architecture

Modern factory automation relies on reliable industrial networking infrastructure to exchange real-time field data across operational technology systems. Engineers often encounter networking hardware like hubs, switches, and routers when integrating Programmable Logic Controllers, Distributed Control Systems, and SCADA monitoring nodes. Although these devices share physical ports, they operate at different layers of the Open Systems Interconnection reference model and deliver distinct traffic management capabilities.

Read more