Product Details

Overview

The Honeywell CC-PDOB01 is a 24V digital output module engineered for Experion Series C I/O systems. It provides 32 fully isolated channels capable of switching resistive and inductive loads. This module is suitable for controlling field devices, relay extensions, and automation outputs in industrial environments.

Technical Specifications

  • Manufacturer: Honeywell

  • Model Number: CC-PDOB01

  • Product Type: 24V Digital Output Module

  • IOTA Model Variants:

    • CC-TDOR01 Non-Redundant 6"

    • CC-TDOR11 Redundant 12"

    • CC-SDOR01 Relay Extension 12"

  • Number of Channels: 32 isolated

  • Contact Form: Form A (SPST/NO) or Form B (SPST/NC), jumper selectable per channel

  • Contact Material: AgSnO

  • Maximum Load Voltage: 250 VAC / 125 VDC

  • Maximum Steady-State Load Current (Resistive):

    • 3A @ 125/250 VAC

    • 3A @ 30 VDC

    • 1A @ 48 VDC

    • 0.2A @ 125 VDC

  • Maximum Steady-State Load Current (Inductive):

    • 2A @ 125/250 VAC (0.4 PF)

    • 1A @ 30 VAC (L/R =100 ms)

    • 0.3A @ 48 VAC (L/R =100 ms)

    • 0.1A @ 125 VAC (L/R =100 ms)

  • Minimum Load Voltage: 12 VDC

  • Minimum Load Current: 100 mA

  • Maximum Inrush Current: 10 A for 4s at 10% duty cycle

  • Turn-On Time: <20 ms

  • Turn-Off Time: <20 ms

  • Isolation: 1500 VAC RMS / ±1500 VDC channel-to-channel and channel-to-logic common

  • Mechanical Life: 5,000,000 cycles (@180 cycles/min)

  • Electrical Life: 50,000 cycles @6A (6 cycles/min)

  • Additional Features: Surge absorber 120 Ω + 0.033 μF per channel

Applications

  • Controlling solenoid valves, actuators, and relays in process automation

  • Integration into Experion PKS Series C distributed control systems

  • Switching both AC and DC loads with high-speed response

FAQ

Q: How many channels does the module provide?
A: The module provides 32 fully isolated digital output channels.

Q: What types of loads can it handle?
A: Supports resistive and inductive loads up to 250 VAC or 125 VDC with proper current ratings.

Q: What is the maximum turn-on/off speed?
A: Turn-on and turn-off times are both under 20 ms.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Preventing Emergency Stop Spurious Trips in Industrial Control Systems

Preventing Emergency Stop Spurious Trips in Industrial Control Systems

Emergency Stop pushbuttons use Normally Closed contacts for fail-safe safety, but mechanical wear can cause costly spurious trips. This technical guide examines E-Stop contact failure root causes, redundant hardware setups, PLC logic monitoring, and maintenance strategies to maximize plant availability.

Read more
Why 24V DC Is the Universal Standard for Industrial Automation Power Supplies

Why 24V DC Is the Universal Standard for Industrial Automation Power Supplies

Industrial manufacturing requires continuous uptime to prevent equipment damage. Unlike AC power, 24V DC circuits seamlessly integrate with UPS units and battery banks. During main grid failures, a 24V DC backup system instantly maintains PLC memory, instrument loops, and critical safety valves without interruption.

Read more
Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

The Site Acceptance Test (SAT) represents the definitive handover stage in industrial automation projects. While the Factory Acceptance Test confirms cabinet hardware assembly off-site, the SAT validates real-world performance under live site conditions. Consequently, a structured execution strategy prevents equipment damage and guarantees seamless integration into plant operations.

Read more