Skip to content

What are you looking for?


You may also like

General Electric DS200TCDAG1A Digital I/O BoardGeneral Electric DS200TCDAG1A Digital I/O BoardGeneral Electric DS200TCDAG1A Digital I/O Board
General Electric DS200TCDAG1A Digital I/O Board
General Electric DS200TCDAG1A Digital I/O Board
General Electric DS200TCDAG1A Digital I/O Board

General Electric DS200TCDAG1A Digital I/O Board


Only 10 left - Selling fast

PRODUCT SKU : DS200TCDAG1A

PRODUCT TYPE : Digital I/O Boards

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The General Electric DS200TCDAG1A, also cataloged as the DS200TCDA Digital I/O Board, operates as a dedicated hardware component for digital signal processing and I/O core communication within Mark V LM control platforms.

Hardware Specifications

Parameter Specification
Model DS200TCDAG1A
Brand General Electric
Origin USA
Dimensions Standard Mark V PCB footprint
Operating Temp Per Mark V environmental standards
Power Consumption Distributed via TCPS board (JP connector)
Core Placement Q11, Q21, or Q51 digital I/O cores
Communication IONET serial interface

Profinet / EtherNet/IP Deterministic Networks and IONET Compatibility

The DS200TCDAG1A interfaces with the IONET (I/O Network) to facilitate deterministic data exchange between the I/O engine and digital cores. The board processes contact output signals for relay/solenoid actuation and accepts digital input signals from terminal boards such as DTBA and DTBB. System architecture requires firmware flash compatibility between the TCDA board and the host controller to ensure synchronized data routing across the I/O network. Deterministic timing is maintained through address-specific data packets directed to the designated core (Q11, Q21, or Q51), with signal propagation confirmed via the backplane interface to the CTBA or TCQC modules.

Frequently Asked Questions

Q: Are the TCDA connectors JP, JQ, JR, JO1, and JO2 interchangeable?

A: No. Each connector has a specific function: JP handles power distribution, JQ and JR interface with DTBA/DTBB terminal boards for input signals, and JO1/JO2 route relay/solenoid output signals to the TCRA board. Improper connection will result in system faults.

Q: Is the TCDA board utilized in all digital I/O cores?

A: The board is designed for placement in Q11, Q21, and Q51 cores. Note that connector JO1 is not utilized in Q11, as the TCQE board in R1 performs the relay control function for that location.

Field Installation Guidelines

  • Mounting: Ensure the board is correctly seated in the designated core (Q11, Q21, or Q51). Verify that the card locks are engaged to prevent vibration-induced disconnection from the backplane.
  • Connector Integrity: Use only the designated cables for JQ and JR connections to ensure proper signal path continuity from the terminal boards.
  • Grounding: Ensure the chassis ground connection is solid to protect the low-voltage IONET signal paths from electromagnetic interference.
  • Wiring: Verify that ribbon cables are routed cleanly and not subjected to tension. When disconnecting, handle connectors by the housing to prevent pin bending.
  • Firmware Verification: After installation, confirm that the system software acknowledges the TCDA board within the designated digital I/O core to ensure the IONET communication handshake is successfully established.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why 24V DC Power Supplies Standardize Modern Industrial Automation

Why 24V DC Power Supplies Standardize Modern Industrial Automation

Industrial control cabinets worldwide rely on 24V DC as the universal power standard for field instrumentation, sensors, and controllers. Walk into any manufacturing plant, and you will find PLCs, human-machine interfaces (HMIs), and smart actuators running on extra-low voltage DC. Standardizing on 24V DC enhances operational safety, lowers cabinet footprint, and maintains steady control performance across factory networks.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
Mastering Modern Industrial Joystick Controls in Heavy Automation

Mastering Modern Industrial Joystick Controls in Heavy Automation

Industrial joysticks play a pivotal role in human-machine interaction across heavy material handling and mobile hydraulics. These tactile controllers translate complex operator movements into precise electrical signals for PLCs, motion controllers, and DCS networks. Consequently, selecting and installing the right joystick architecture ensures operator safety, reduces fatigue, and optimizes equipment performance.

Read more