GE IC695ALG708 PACSystems RX3i Analog Output ModuleGE IC695ALG708 PACSystems RX3i Analog Output ModuleGE IC695ALG708 PACSystems RX3i Analog Output Module
GE IC695ALG708 PACSystems RX3i Analog Output Module
GE IC695ALG708 PACSystems RX3i Analog Output Module
GE IC695ALG708 PACSystems RX3i Analog Output Module

GE IC695ALG708 PACSystems RX3i Analog Output Module


Only 10 left - Selling fast

PRODUCT SKU : IC695ALG708

PRODUCT TYPE : Analog Output Module

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Overview

The IC695ALG708 from GE is a non-isolated 8-channel analog output module designed for RX3i PACSystems. It supports both voltage and current outputs with high-resolution performance and precise timing, making it suitable for applications requiring accurate analog control.

Technical Specifications

  • Module Type: Non-isolated analog output

  • Channels: 8

  • Voltage Output Range: 0–10 V, ±10 V

  • Current Output Range: 0–20 mA, 4–20 mA

  • Resolution:

    • ±10 V: 15.9 bits

    • 0–10 V: 14.9 bits

    • 0–20 mA: 15.9 bits

    • 4–20 mA: 15.6 bits

  • Maximum Load: 850 Ω

  • Data Format: Floating point IEEE 32-bit or 16-bit integer in 32-bit field

  • Update Rate: 8 ms (all channels)

  • Output Settling Time: 2 ms (0–95%)

  • Isolation Voltage (Field to Backplane): 2550 VDC for 1 second

  • Power Consumption: 375 mA at 3.3 VDC, 315 mA at 24 VDC

  • Maximum Module Power Dissipation: 7.25 W

  • External Supply Voltage: 19.2–30 V (24 V nominal)

  • External Current Input: 210 mA

  • HART Protocol: Not supported

Mechanical & Environmental

  • Weight: 0.94 lbs (0.43 kg)

  • Series: PACSystems RX3i

  • Operating Temperature: 0–60 °C

  • Power Dissipation (Vuser=24V): 7.25 W maximum

Applications

The IC695ALG708 is ideal for controlling analog devices such as actuators, valves, and control loops within RX3i automation systems where precise voltage and current output is required.

FAQ

  • Q: Can this module support HART communication?
    A: No, HART protocol is not supported.

  • Q: What is the maximum output load?
    A: 850 Ω for current and voltage outputs.

  • Q: Is the module hot-swappable?
    A: Yes, the RX3i backplane supports module replacement without powering down the system.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why 24V DC Is the Universal Standard for Industrial Automation Power Supplies

Why 24V DC Is the Universal Standard for Industrial Automation Power Supplies

Industrial manufacturing requires continuous uptime to prevent equipment damage. Unlike AC power, 24V DC circuits seamlessly integrate with UPS units and battery banks. During main grid failures, a 24V DC backup system instantly maintains PLC memory, instrument loops, and critical safety valves without interruption.

Read more
Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

The Site Acceptance Test (SAT) represents the definitive handover stage in industrial automation projects. While the Factory Acceptance Test confirms cabinet hardware assembly off-site, the SAT validates real-world performance under live site conditions. Consequently, a structured execution strategy prevents equipment damage and guarantees seamless integration into plant operations.

Read more
Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

The Factory Acceptance Test (FAT) is a vital milestone in industrial automation that ensures custom PLC panels meet exact design specifications before dispatch. This guide outlines the step-by-step FAT procedure and key industry best practices to prevent costly site delays and ensure long-term operational success.

Read more