Configured for multi-channel analog signal acquisition in Honeywell Experion PKS platforms, the Honeywell FC-TSAL-1620M (FC-TSAL-1620M Analog Input Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model FC-TSAL-1620M
Brand Honeywell
Origin USA
Weight 0.95 lbs (0.43 kg)
Dimensions 210 x 70 x 60 mm / 137 x 40 x 147 mm
Operating Temp -40 to +70 deg C
Power Consumption Internal processing voltage 0-4 VDC
Input Channels 16 analog input channels
Supported Input Types 4-20 mA, 0-5 V, thermocouples
Signal Range 0-22 mA / 0-5.5 V
Resolution & Accuracy 16-bit, +/-0.1% of full scale
Input Resistance >= 100 kOhm
Fuse Rating 315 mA

Channel-to-Channel Isolation & Signal Integrity

The FC-TSAL-1620M incorporates complete channel-to-channel and channel-to-earth galvanic isolation across all 16 input paths to guarantee high noise rejection. Designed for integration with 4-20 mA HART loop protocol transmitters and voltage signals, the conditioning circuitry preserves high 16-bit resolution accuracy under dynamic industrial noise. The module includes active line diagnosis limits (4-22 mA / 1-5.5 V) that continuously monitor loop integrity, ensuring open-circuit and short-circuit field conditions are detected without disturbing adjacent analog channels.

Frequently Asked Questions

Q: What protection measures prevent high-voltage transients on field loops from damaging the FC-TSAL-1620M backplane circuit?

A: Each channel features individual channel-to-channel and channel-to-earth galvanic isolation, paired with onboard 315 mA fuses to isolate overcurrent conditions locally.

Q: How does the module handle extended input signal levels beyond standard 4-20 mA or 0-5 V limits?

A: The analog input conversion hardware supports an over-range measurement span of 0-22 mA and 0-5.5 V, allowing accurate signal evaluation up to full scale limits.

Field Installation Guidelines

  1. Power down the system chassis or field loop supply prior to inserting the module onto the DIN rail, chassis, or backplane connector.
  2. Route thermocouple and 4-20 mA instrument field cables in dedicated, shielded raceways isolated from high-voltage AC lines.
  3. Verify that all shield drain wires are terminated to a single earth ground point to preserve channel-to-earth isolation performance.
  4. Ensure environmental operating conditions stay within -40 to +70 deg C and relative humidity does not exceed 95% RH (non-condensing).

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Industry 4.0 integrates digital intelligence into field operations, transforming factory automation landscapes worldwide. Spatial technologies—specifically Augmented Reality (AR) and Virtual Reality (VR)—redefine how engineers interact with industrial control systems. By bridging computer-generated CAD models with real-time operational technology (OT) data, immersive displays enable intuitive monitoring, rapid diagnostics, and safer maintenance across complex processing facilities.

Read more
Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) serve as critical quality assurance gateways in complex industrial control systems. Both procedures verify that programmable logic controllers (PLCs), distributed control systems (DCS), and associated field devices meet strict functional specifications. However, executing these tests effectively requires clear delineation between off-site staging and final field commissioning.

Read more
Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial automation relies heavily on robust networking infrastructure to connect programmable logic controllers (PLCs), distributed control systems (DCS), and human-machine interfaces (HMIs). Modern factory automation environments generate vast amounts of real-time operational data across deterministic networks. Understanding the structural differences between hubs, switches, and routers ensures optimal traffic segmentation, minimizes latency, and maintains high network availability.

Read more