Skip to content

What are you looking for?


You may also like

AMM22M | Yokogawa mV Input Multiplexer Module for CENTUM CS/VP SystemsAMM22M | Yokogawa mV Input Multiplexer Module for CENTUM CS/VP SystemsAMM22M | Yokogawa mV Input Multiplexer Module for CENTUM CS/VP Systems
AMM22M | Yokogawa mV Input Multiplexer Module for CENTUM CS/VP Systems
AMM22M | Yokogawa mV Input Multiplexer Module for CENTUM CS/VP Systems
AMM22M | Yokogawa mV Input Multiplexer Module for CENTUM CS/VP Systems

AMM22M | Yokogawa mV Input Multiplexer Module for CENTUM CS/VP Systems


Only 10 left - Selling fast

PRODUCT SKU : AMM22M

PRODUCT TYPE : Input Multiplexer Module

PRODUCT VENDOR : Yokogawa


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Yokogawa AMM22M mV Input Multiplexer Module 

The Yokogawa AMM22M is a high-precision millivolt (mV) input multiplexer module designed for the CENTUM CS and CENTUM VP distributed control systems. It solves the challenge of acquiring accurate low-voltage signals from extensive sensor arrays by consolidating up to 22 analog input channels into a single, compact unit. This module is essential for industrial applications requiring high-density data collection, such as temperature monitoring via thermocouples or strain gauge measurements, ensuring signal integrity and system reliability in complex automation environments.

Technical Specifications

The AMM22M is engineered for high input impedance and exceptional accuracy in low-level signal processing.

Parameter Specification
Product Type mV Input Multiplexer Module
Model Number AMM22M
Compatible Systems CENTUM CS, CENTUM VP
Input Channels 22 Analog Input Channels
Input Signal Range -100 mV to +100 mV DC
Allowable Input Voltage -0.5 V to +4.0 V DC
Input Resistance 1 MΩ (E1 MΩ)
Accuracy ±40 µV (Microvolts)
Burnout Detection Selectable (UP / DOWN / OFF)
Disconnection Detection ≤ 10 seconds response time
Data Update Period 1 second
Dimensions 12.7 cm x 2.5 cm x 20.3 cm
Weight 0.2 kg

Model Code Interpretation

For Yokogawa modules, the suffix codes provide critical information about the hardware revision and interface type.

Part Number: AMM22M

AMM22-AXX

  • A (Suffix -M): This suffix typically designates the specific hardware revision or "Modified" version.

    • -M: In the context of the AMM series, this often indicates a specific iteration designed for enhanced performance or compatibility with updated carrier standards (such as the AMN32 or AMN34). It distinguishes the unit from earlier revisions (like the base AMM22) which may have different channel counts or isolation specifications.

Note: Always verify the suffix on the module label to ensure it matches the engineering specifications for your specific CENTUM system configuration.

Installation and Wiring Guidelines

Proper installation is crucial to maintain the high accuracy (±40 µV) specified for the AMM22M.

  1. Carrier Installation: The AMM22M is designed to be mounted in specific I/O carrier boxes (such as the AMN series). Slide the module into the designated slot until it locks securely into the backplane.

  2. Wiring for Low-Voltage Signals:

    • Shielding: Because the module handles low-level mV signals, it is highly susceptible to electrical noise. You must use high-quality shielded twisted-pair cables for all connections.

    • Grounding: Ground the cable shield at the control cabinet end (single-point grounding) to prevent ground loops, which can introduce significant measurement errors.

  3. Burnout Configuration: Before commissioning, configure the burnout detection settings (UP, DOWN, or OFF) via the system engineering software. This ensures the system correctly identifies sensor failures (e.g., a broken thermocouple wire).

  4. Input Resistance Check: Ensure the signal source resistance is within the allowable limit (≤ 1 kΩ) to maintain measurement accuracy. High source resistance can lead to voltage drops and reading errors.

Frequently Asked Questions (FAQ)

Q: What is the primary application for the AMM22M?A: The AMM22M is primarily used for measuring low-voltage signals, such as those from thermocouples, strain gauges, or other millivolt-output sensors. Its high input resistance (1 MΩ) makes it ideal for these sensitive applications.

Q: How does the burnout detection feature work?A: The module can be configured to detect open circuits (sensor breakage). If a disconnection occurs, the module drives the signal upscale (UP) or downscale (DOWN) to alert the operator, depending on the user configuration.

Q: Is the AMM22M compatible with CENTUM VP?A: Yes, this module is fully compatible with both CENTUM CS and CENTUM VP systems, allowing for seamless integration and upgrades within existing control architectures.

Q: What does "E1 MΩ" input resistance mean?A: This indicates a very high input impedance (typically 1 Megaohm). High impedance ensures that the module draws minimal current from the signal source, preventing the measurement device from loading the circuit and altering the voltage reading.

Shopify SEO Data

SEO Title:Yokogawa AMM22M mV Multiplexer | CENTUM CS/VP Module | In Stock

Meta Description:Genuine Yokogawa AMM22M mV Input Multiplexer. 22-Channel High Precision for CENTUM VP/CS. Brand New, In Stock & Fast Shipping. Order Today.

 

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

System reliability directly determines operational profitability across high stakes process industries. Modern industrial automation platforms must eliminate single points of failure to prevent catastrophic shutdowns. Deploying fault tolerant architecture safeguards complex facilities against unexpected hardware glitches, network disruptions, and maintenance outages.

Read more
Understanding Types of Noise in Electronic Circuits and Control Systems

Understanding Types of Noise in Electronic Circuits and Control Systems

Signal integrity directly determines measurement accuracy and loop stability across industrial automation environments. Electronic noise introduces unwanted stochastic interference into analog loops, sensor feedback lines, and digital fieldbus networks. Understanding how intrinsic electronic noise and external electromagnetic interference manifest allows control engineers to optimize signal conditioning and shield sensitive instrumentation effectively.

Read more
Why 24V DC Power Supplies Standardize Modern Industrial Automation

Why 24V DC Power Supplies Standardize Modern Industrial Automation

Industrial control cabinets worldwide rely on 24V DC as the universal power standard for field instrumentation, sensors, and controllers. Walk into any manufacturing plant, and you will find PLCs, human-machine interfaces (HMIs), and smart actuators running on extra-low voltage DC. Standardizing on 24V DC enhances operational safety, lowers cabinet footprint, and maintains steady control performance across factory networks.

Read more