Overview

The Allen-Bradley 1746-NI16I is a 16-channel SLC 500 analog input module designed for precise signal acquisition in control systems. It supports multiple current input ranges, high-resolution sigma-delta conversion, and features robust isolation for reliable operation in industrial environments.

Technical Specifications

  • Manufacturer: Allen-Bradley (Rockwell Automation)

  • Model / Part Number: 1746-NI16I

  • Product Type: Analog Input Module

  • Product Line: SLC 500

  • Number of Inputs: 16 channels

  • Input Signal Types: 0–20 mA, 4–20 mA, ±20 mA, 0–1 mA

  • Bandwidth: 6–250 Hz

  • Step Response: 9–630 ms

  • Input Filtering: Low-pass digital filter with programmable frequencies (6, 10, 20, 40, 60, 80, 100, 250 Hz)

  • Conversion Type: Sigma-Delta

  • Backplane Current: 125 mA @ 5 VDC; 75 mA @ 24 VDC

  • Isolation: 500 V AC for 1 second (channel-to-backplane)

  • LED Indicators: 5 green LEDs (one per group of four channels) plus module status indicator

  • Chassis Location: Any I/O slot except slot 0

  • Thermal Dissipation: 2.43 W

  • Recommended Cabling: Belden #8761 or equivalent

Key Features

  • Supports multiple analog current ranges for flexible system integration

  • 16 individually monitored channels with group status indicators

  • Sigma-Delta A/D conversion for precise analog-to-digital performance

  • Digital low-pass filtering reduces signal noise

  • High isolation voltage ensures system reliability

Applications

  • Process monitoring and measurement in SLC 500 systems

  • Integration with 120V AC I/O and other analog devices

  • Industrial automation requiring high-accuracy analog signal inputs

FAQs

Q1: What input signal ranges does 1746-NI16I support?
It supports 0–20 mA, 4–20 mA, ±20 mA, and 0–1 mA signals.

Q2: How is channel status indicated?
Each group of four channels has a green LED, with an additional LED for module status.

Q3: What isolation does the module provide?
The module provides 500 V AC isolation for 1 second, protecting the backplane and input signals.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why 24V DC Is the Universal Standard for Industrial Automation Power Supplies

Why 24V DC Is the Universal Standard for Industrial Automation Power Supplies

Industrial manufacturing requires continuous uptime to prevent equipment damage. Unlike AC power, 24V DC circuits seamlessly integrate with UPS units and battery banks. During main grid failures, a 24V DC backup system instantly maintains PLC memory, instrument loops, and critical safety valves without interruption.

Read more
Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

The Site Acceptance Test (SAT) represents the definitive handover stage in industrial automation projects. While the Factory Acceptance Test confirms cabinet hardware assembly off-site, the SAT validates real-world performance under live site conditions. Consequently, a structured execution strategy prevents equipment damage and guarantees seamless integration into plant operations.

Read more
Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

The Factory Acceptance Test (FAT) is a vital milestone in industrial automation that ensures custom PLC panels meet exact design specifications before dispatch. This guide outlines the step-by-step FAT procedure and key industry best practices to prevent costly site delays and ensure long-term operational success.

Read more