Skip to content

What are you looking for?


You may also like

AAI143-H00/K4A00 | Yokogawa CENTUM VP 16-Channel HART Isolated Analog Input ModuleAAI143-H00/K4A00 | Yokogawa CENTUM VP 16-Channel HART Isolated Analog Input ModuleAAI143-H00/K4A00 | Yokogawa CENTUM VP 16-Channel HART Isolated Analog Input Module
AAI143-H00/K4A00 | Yokogawa CENTUM VP 16-Channel HART Isolated Analog Input Module
AAI143-H00/K4A00 | Yokogawa CENTUM VP 16-Channel HART Isolated Analog Input Module
AAI143-H00/K4A00 | Yokogawa CENTUM VP 16-Channel HART Isolated Analog Input Module

AAI143-H00/K4A00 | Yokogawa CENTUM VP 16-Channel HART Isolated Analog Input Module


Only 10 left - Selling fast

PRODUCT SKU : AAI143-H00/K4A00

PRODUCT TYPE : Analog Input Module

PRODUCT VENDOR : Yokogawa


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Description

The AAI143-H00/K4A00 from Yokogawa is a robust analog input module designed for distributed control systems. It provides 16 isolated input channels capable of handling 4–20 mA DC signals, ensuring accurate and stable data acquisition in industrial automation environments.

This model supports HART communication, enabling remote diagnostics and transmitter configuration. The suffix codes define its configuration: “H” indicates HART protocol support, “0” denotes the basic type, and “/K4A00” specifies the inclusion of a KS cable interface adapter (ATK4A-00) for connecting to terminal boards.

Technical Specifications

  • Model / Order Number: AAI143-H00/K4A00

  • Manufacturer: Yokogawa Electric Corporation

  • Type: Analog Input Module

  • Channels: 16 isolated analog inputs

  • Signal Range: 4–20 mA DC

  • Allowable Input Current: Up to 24 mA

  • Input Resistance:

    • Power ON: 270 Ω (20 mA) to 350 Ω (4 mA)

    • Power OFF: ≥500 kΩ

  • Accuracy: ±16 µA

  • Temperature Drift: ±16 µA per 10°C

  • Data Update Period: 10 ms

  • Transmitter Power Supply: 19.0–25.5 V (current limit 25 mA)

  • Isolation Voltage: 1500 V AC between input and system (1 minute)

  • Current Consumption: 230 mA (5 V DC), 540 mA (24 V DC)

  • External Connections: Pressure clamp terminal, MIL connector cable, KS cable

  • Weight: Approx. 0.3 kg

Application Scenarios

  • Signal acquisition from field transmitters in process industries

  • Integration into Yokogawa CENTUM VP and CS 3000 systems

  • Environments requiring HART communication for diagnostics and configuration

  • Safety‑critical monitoring in petrochemical, oil & gas, and power generation

FAQ

Q: How many channels does the AAI143-H00/K4A00 support?  A: It provides 16 isolated analog input channels.

Q: What does the /K4A00 option mean?  A: It indicates the module is supplied with a KS cable interface adapter (ATK4A-00).

Q: Does the module support HART communication?  A: Yes, the “H” suffix confirms HART protocol compatibility.

Q: What is the accuracy of this module?  A: ±16 µA across the rated input range.

Q: Is the module explosion‑proof?  A: No, the suffix “5” specifies that it is a non‑explosion protected type.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

Site Acceptance Testing (SAT) for PLC Control Systems: An Engineering Execution Guide

The Site Acceptance Test (SAT) represents the definitive handover stage in industrial automation projects. While the Factory Acceptance Test confirms cabinet hardware assembly off-site, the SAT validates real-world performance under live site conditions. Consequently, a structured execution strategy prevents equipment damage and guarantees seamless integration into plant operations.

Read more
Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

Mastering the Factory Acceptance Test (FAT) for PLC Control Panels: An Expert Guide

The Factory Acceptance Test (FAT) is a vital milestone in industrial automation that ensures custom PLC panels meet exact design specifications before dispatch. This guide outlines the step-by-step FAT procedure and key industry best practices to prevent costly site delays and ensure long-term operational success.

Read more
Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

System reliability directly determines operational profitability across high stakes process industries. Modern industrial automation platforms must eliminate single points of failure to prevent catastrophic shutdowns. Deploying fault tolerant architecture safeguards complex facilities against unexpected hardware glitches, network disruptions, and maintenance outages.

Read more