The Triconex 2401 is a 16-channel analog output module designed for signal generation within Triconex Triple Modular Redundant (TMR) safety instrumented systems. Operating within a Tricon chassis with under 12 W power consumption, this plug-in card delivers software-configurable 4-20 mA current or 0-10 VDC voltage output signals directly to control valves, positioners, and field actuators.

Digital-to-Analog Performance and Loop Diagnostics

Each of the 16 output channels utilizes 12-bit D/A conversion, achieving full-scale accuracy of ±0.1% and repeatability within ±0.05% of span. The module incorporates continuous self-diagnostics with dynamic fault reporting to the Tricon main processor, alongside field loop monitoring to identify open or short circuit conditions and support Sequence of Events (SOE) timestamping.

Isolation and Physical Construction

To protect internal processing logic, optical isolation is provided between field circuits and chassis backplane electronics, while individual channels are isolated to prevent cross-channel noise interference. The unit measures approximately 17.3 in × 7.2 in × 13.0 in, weighs 6.5 kg (14 lbs), and operates reliably across an extended temperature range from -40 deg C to +70 deg C (-40 deg C to +85 deg C storage) under 5% to 95% non-condensing humidity.

Specifications

Parameter Specification
Model 2401
Brand Triconex
Series Tricon
Architecture Triple Modular Redundancy (TMR)
Product Type Analog Output Module
Output Channels 16 analog output channels
Configurable Signal Ranges 4-20 mA current output, 0-10 VDC voltage output
D/A Resolution 12-bit
Output Accuracy ±0.1% of full scale
Repeatability ±0.05% of span
Diagnostics & Monitoring Continuous self-diagnostics, fault reporting to controller, loop monitoring
Isolation Optical isolation (field-to-logic) and channel-to-channel noise isolation
Power Consumption < 12 W (supplied via Tricon backplane)
Operating Temperature -40 deg C to +70 deg C
Storage Temperature -40 deg C to +85 deg C
Relative Humidity 5% to 95% (non-condensing)
Form Factor Plug-in card for Tricon chassis
Dimensions Approx. 17.3 in × 7.2 in × 13.0 in
Weight 6.5 kg (14 lbs)

Frequently Asked Questions

Q: What output signal ranges are supported by the Triconex 2401 module?

A: The module features 16 output channels configurable for either 4-20 mA current output or 0-10 VDC voltage output.

Q: What level of conversion accuracy and resolution does the 2401 analog output module offer?

A: It provides 12-bit digital-to-analog conversion with an accuracy of ±0.1% of full scale and repeatability of ±0.05% of span.

Q: What diagnostic capabilities are integrated into the Triconex 2401?

A: The module executes continuous self-diagnostics, automatically reports hardware faults to the main controller, and monitors field loops for open or short circuits.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more