PRODUCT SKU : 900А16-0103

PRODUCT TYPE : Analog Input Modules

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Honeywell 900A16-0103, also cataloged as the 900A16 High Level Analog Input Module, operates as a dedicated hardware component for high-density analog voltage signal acquisition within ControlEdge 900 platform architectures.

Hardware Specifications

Parameter Specification
Model 900A16-0103
Brand Honeywell
Origin USA
Weight 1.00 lbs (0.45 kg)
Dimensions Standard ControlEdge 900 module form factor
Operating Temp 0 deg C to 60 deg C
Power Consumption 75 mA max at 5 VDC and 50 mA max at 24 VDC
Secondary Part Number 50008235-002
Channel Density 16 channels
Input Signal Range +/- 10 VDC
Update Rate 100 ms
Leakage Current 2 uA max/channel
Product Category PLCs/Machine Control / VDC Logic I/O Module

Channel-to-Channel Isolation & Process Control Interconnection

The 900A16-0103 module acquires +/- 10 VDC high-level voltage inputs across 16 isolated channels with a 100 ms scan execution time. Built to integrate within process control racks processing 4-20 mA HART loop protocol instruments, the module's input circuitry enforces strict channel-to-channel isolation. This limits current leakage to 2 uA max per channel, preventing signal attenuation and electrical ground loops across differential measurement points.

Frequently Asked Questions

Q: What are the backplane power supply current requirements for the 900A16-0103 module?

A: The module draws a maximum backplane load of 75 mA at 5 VDC and 50 mA at 24 VDC.

Q: What is the maximum channel scan rate for the 16 analog input signals?

A: All 16 channels are processed continuously with an update interval of 100 ms.

Field Installation Guidelines

  1. Power down the controller rack backplane before inserting or removing the module from its slot.
  2. Route high-level voltage signal wiring using twisted-pair shielded cable, grounding the cable shield at a single termination point on the rack chassis.
  3. Keep field input conductors separated from high-voltage AC cables in wire ducts to prevent capacitive crosstalk.
  4. Verify all field wiring terminals are fully seated and tightened to prevent loose high-resistance analog sensor connections.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Industry 4.0 integrates digital intelligence into field operations, transforming factory automation landscapes worldwide. Spatial technologies—specifically Augmented Reality (AR) and Virtual Reality (VR)—redefine how engineers interact with industrial control systems. By bridging computer-generated CAD models with real-time operational technology (OT) data, immersive displays enable intuitive monitoring, rapid diagnostics, and safer maintenance across complex processing facilities.

Read more
Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) serve as critical quality assurance gateways in complex industrial control systems. Both procedures verify that programmable logic controllers (PLCs), distributed control systems (DCS), and associated field devices meet strict functional specifications. However, executing these tests effectively requires clear delineation between off-site staging and final field commissioning.

Read more
Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial Networking Essentials: Demystifying Hubs, Switches, and Routers in Control Systems

Industrial automation relies heavily on robust networking infrastructure to connect programmable logic controllers (PLCs), distributed control systems (DCS), and human-machine interfaces (HMIs). Modern factory automation environments generate vast amounts of real-time operational data across deterministic networks. Understanding the structural differences between hubs, switches, and routers ensures optimal traffic segmentation, minimizes latency, and maintains high network availability.

Read more