Product Details
The Honeywell BC1000A0110U, also cataloged as the BC1000A Flame Switch Controller, operates as a dedicated hardware component for continuous optical flame sensing and safe start interlock monitoring within industrial burner control systems. Operating on 115 VAC line power, it processes signals from rectifying flame rods or non-self-check UV sensors to actuate internal safe start check and flame relay contact outputs.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BC1000A0110U |
| Brand | Honeywell |
| Origin | Industrial Standard Assembly |
| Weight | 0.50 kg |
| Dimensions | Standard DIN Panel Mounting Module Dimensions |
| Operating Temp | -40 to +60 deg C (-40 to +140 deg F) |
| Power Consumption | 8 W |
| Input Voltage | 115 VAC, 50/60 Hz |
| Response Time | 2 +/- 1 sec |
| Sensor Compatibility | Rectifying Flame Rods, C7027, C7035, C7044, C7927 UV Sensors |
| Output Relay Contacts | SPST (T3-4) Safe Start Check, SPST (T2-3) Flame |
| Mounting Options | DIN Rail or Direct Panel Mounting |
4-20 mA HART Loop Protocol & DCS Integration
The BC1000A0110U incorporates channel-to-channel isolation parameters that decouple line-voltage relay switching circuits from low-voltage microelectronic flame signal processing paths. This galvanic barrier isolates incoming sensor signals against line transients and high-frequency noise induced by surrounding field hardware. Maintaining signal pathway separation prevents interference when transmitting flame status signals alongside co-located 4-20 mA HART loop protocol transmitters and central DCS monitoring equipment within the control panel network.
Frequently Asked Questions
Q: Which specific Honeywell UV sensor models are compatible with the BC1000A0110U?
A: The controller interfaces directly with non-self-check UV sensor models C7027, C7035, C7044, and C7927, as well as standard rectifying flame rods.
Q: What is the trip execution timing when a flame failure condition occurs?
A: The internal relay circuit drops out to execute a fail-safe contact transition within 2 +/- 1 seconds of flame signal loss.
Q: Can the unit be mounted on standard industrial enclosure rails?
A: Yes, the housing enclosure supports mounting on standard DIN rails as well as direct flat-panel screw fastening.
Field Installation Guidelines
- Disconnect all primary power supplies and line-voltage loads before installing or servicing the BC1000A0110U unit.
- Secure the controller to the DIN rail or panel surface ensuring proper physical alignment and grounding contact.
- Route flame sensor wiring in separate grounded steel conduit away from high-voltage ignition cables to prevent induced stray currents.
- Wire 115 VAC line power and output relays (T3-4 Safe Start Check, T2-3 Flame) strictly according to the terminal connection diagram prior to energizing the system.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.