Only 10 left - Selling fast

PRODUCT SKU : 900А16-0103

PRODUCT TYPE : Analog Input Modules

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Honeywell 900A16-0103, also cataloged as the 900A16 High Level Analog Input Module, operates as a dedicated hardware component for high-density analog voltage signal acquisition within ControlEdge 900 platform architectures.

Hardware Specifications

Parameter Specification
Model 900A16-0103
Brand Honeywell
Origin USA
Weight 1.00 lbs (0.45 kg)
Dimensions Standard ControlEdge 900 module form factor
Operating Temp 0 deg C to 60 deg C
Power Consumption 75 mA max at 5 VDC and 50 mA max at 24 VDC
Secondary Part Number 50008235-002
Channel Density 16 channels
Input Signal Range +/- 10 VDC
Update Rate 100 ms
Leakage Current 2 uA max/channel
Product Category PLCs/Machine Control / VDC Logic I/O Module

Channel-to-Channel Isolation & Process Control Interconnection

The 900A16-0103 module acquires +/- 10 VDC high-level voltage inputs across 16 isolated channels with a 100 ms scan execution time. Built to integrate within process control racks processing 4-20 mA HART loop protocol instruments, the module's input circuitry enforces strict channel-to-channel isolation. This limits current leakage to 2 uA max per channel, preventing signal attenuation and electrical ground loops across differential measurement points.

Frequently Asked Questions

Q: What are the backplane power supply current requirements for the 900A16-0103 module?

A: The module draws a maximum backplane load of 75 mA at 5 VDC and 50 mA at 24 VDC.

Q: What is the maximum channel scan rate for the 16 analog input signals?

A: All 16 channels are processed continuously with an update interval of 100 ms.

Field Installation Guidelines

  1. Power down the controller rack backplane before inserting or removing the module from its slot.
  2. Route high-level voltage signal wiring using twisted-pair shielded cable, grounding the cable shield at a single termination point on the rack chassis.
  3. Keep field input conductors separated from high-voltage AC cables in wire ducts to prevent capacitive crosstalk.
  4. Verify all field wiring terminals are fully seated and tightened to prevent loose high-resistance analog sensor connections.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.