Product Details

Configured for high-speed network integration within Mark V and EX2000 control platforms, the GE DS200SLCCG3A (DS200SLCC LAN Communication Card) provides direct physical/electrical execution of LAN-based controller communication.

Hardware Specifications

Parameter Specification
Model DS200SLCCG3A
Brand General Electric
Origin USA
Dimensions Standard Mark V PCB footprint
Operating Temp Per Mark V environmental standards
Power Consumption Backplane rail supply
Processor LAN Control Processor (U1)
Interface 16-position alphanumeric display

Industrial Control and Firmware Compatibility

The DS200SLCCG3A facilitates deterministic data exchange across the Mark V backplane. Proper operation is contingent upon backplane bus communication velocity settings that synchronize the LAN control processor with the driver controller processor (DCP) on the SDCC board. Firmware flash compatibility is managed via replaceable EPROMS (U6, U7), which house the LCP software stack. Any replacement of these memory modules requires strict adherence to checksum validation to ensure data integrity during LCP execution. I/O density scaling is supported through the board's dual-ported RAM (U5) architecture, which regulates the data handshaking between the LAN controller and host drive electronics.

Frequently Asked Questions

Q: How is the LCP software updated on the SLCC board?

A: The LCP software is stored in replaceable EPROMS located at U6 and U7. To update, remove the board, extract the existing EPROMS, and install the new programmed EPROMS into the designated sockets while observing static discharge precautions.

Q: What is the purpose of the connector labeled KPPL?

A: The KPPL connector serves as the interface for the programmer module. This module allows operators to perform diagnostic testing, adjust software parameters, and view fault codes via the 16-position alphanumeric display.

Field Installation Guidelines

  • Static Sensitivity: The SLCC board utilizes sensitive CMOS components. Always wear a grounded anti-static wrist strap when handling the PCB to prevent permanent damage to the LCP or memory modules.
  • Connector Alignment: Ensure all system-level connections to the NTB/3TB, SDCC, and TCCB boards via the 2PL connector are fully seated. Improper seating of the 2PL or 3PL connectors can cause communication timeouts between the LCP and the SDCC.
  • Programmer Module: When mounting the programmer module onto the KPPL connector, apply uniform pressure to ensure the pins are correctly aligned and fully engaged to prevent intermittent diagnostic data.
  • Component Verification: Before energizing the cabinet, verify that EPROMS U6 and U7 are oriented correctly according to the notch index on the socket. Reverse installation will result in immediate boot-up failure.
  • Grounding: Ensure the board is properly secured to the cabinet chassis via its mounting screws to maintain the integrity of the isolated and non-isolated circuit grounding paths.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

Executing a PLC System Site Acceptance Test (SAT): The Definitive Engineering Guide

The transition of a Programmable Logic Controller (PLC) cabinet from a controlled factory floor to a volatile plant environment represents a critical milestone in factory automation. While a Factory Acceptance Test (FAT) validates standalone hardware compliance under ideal conditions, it cannot replicate real-world process dynamics. Therefore, deploying an industrial automation system requires a rigorous Site Acceptance Test (SAT) to verify total loop integrity, field wiring wiring metrics, and process control parameters before final customer handover.

Read more
Advanced Integration: Master Protocol for VFD Commissioning and Testing

Advanced Integration: Master Protocol for VFD Commissioning and Testing

Deploying variable frequency drives (VFDs) requires precise execution during the initial commissioning phase. Junior automation engineers often find the first power-up sequence intimidating. However, following a rigorous engineering framework ensures equipment safety and system reliability. Proper startup procedures protect both the drive electronics and the connected motor.

Read more
Optimizing Factory Automation: The Definitive Guide to VFD Preventive Maintenance

Optimizing Factory Automation: The Definitive Guide to VFD Preventive Maintenance

Variable Frequency Drives (VFDs) serve as critical assets in modern industrial automation. These power electronic devices regulate electric motors by adjusting the supplied frequency and voltage. Consequently, industries utilize VFDs to reduce energy consumption and optimize process control. Major manufacturers like Siemens, ABB, and Yaskawa design highly efficient drives. However, sustained efficiency requires a rigorous preventive maintenance program.

Read more