Foxboro P0918AH Analog Input ModuleFoxboro P0918AH Analog Input ModuleFoxboro P0918AH Analog Input Module
Foxboro P0918AH Analog Input Module
Foxboro P0918AH Analog Input Module
Foxboro P0918AH Analog Input Module

Foxboro P0918AH Analog Input Module


Only 10 left - Selling fast

PRODUCT SKU : P0918AH

PRODUCT TYPE : Analog Input Modules

PRODUCT VENDOR : Foxboro


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Foxboro P0918AH, also cataloged as the P0918AH Analog Input Module, operates as a dedicated hardware component for high-density analog signal digitization and real-time process monitoring within Foxboro DCS platforms. It processes 16 analog input channels across current and voltage ranges, converting field signals into 16-bit digital resolution for system controller execution.

Hardware Specifications

Parameter Specification
Model P0918AH
Brand Foxboro
Origin USA
Weight 0.45 kg
Dimensions 172 mm x 107 mm x 61 mm
Operating Temp -40 deg C to +70 deg C
Power Consumption 3.5 W
Input Channels 16 analog inputs
Input Signal Types Current: 4-20 mA; Voltage: 0-10 V, -10 V to +10 V
Resolution 16 bits
Accuracy +-0.1% of full scale
Isolation Voltage 500 VDC between channels
Power Supply 24 VDC
Update Rate 250 ms response time

Channel-to-Channel Isolation and Loop Protocol Integration

The Foxboro P0918AH incorporates 500 VDC galvanic isolation barriers between individual channels to maintain signal integrity and eliminate ground loops across field wiring. This channel-to-channel isolation safeguards 16-bit analog-to-digital conversions against common-mode electrical noise and high-voltage transients while processing 4-20 mA HART loop protocol transmitters and multi-range voltage instruments.

Frequently Asked Questions

Q: What isolation rating is provided between individual channels on the P0918AH module?

A: The P0918AH provides 500 VDC galvanic isolation between input channels to protect logic circuits against potential ground fault currents.

Q: What is the sampling update rate across all 16 channels of the P0918AH module?

A: The module executes a maximum response time of 250 ms across its input channels for real-time control loop updating.

Field Installation Guidelines

Mount the P0918AH module vertically into its designated baseplate card slot, verifying that upper and lower mechanical retention clips engage fully with the chassis rails. Ensure 24 VDC system supply power is de-energized prior to seating or removing the module.

Route all analog field input wiring through dedicated low-voltage wiring ductwork, physically separated from high-voltage AC cables and motor drives. Connect all signal cable drain shields to the main cabinet single-point ground bar. For conduit penetrations entering the cabinet enclosure, ensure all threaded NPT fittings achieve a minimum of 5 full threads of engagement to maintain physical strain relief and grounding integrity.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling Cabinet Preventive Maintenance: Essential Healthiness Checks for PLC, DCS, and ESD Systems

Marshalling cabinets serve as the vital interface between field instrumentation and control room electronics in modern process facilities. Regular preventive maintenance of these cabinets ensures signal integrity across programmable logic controllers (PLCs), distributed control systems (DCS), and emergency shutdown (ESD) networks. System technicians must execute structured inspection protocols to mitigate environmental risks, identify loose wiring, and maintain continuous operational readiness.

Read more
Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Spatial Computing in Industrial Automation: Elevating PLC and DCS Operations with AR and VR

Industry 4.0 integrates digital intelligence into field operations, transforming factory automation landscapes worldwide. Spatial technologies—specifically Augmented Reality (AR) and Virtual Reality (VR)—redefine how engineers interact with industrial control systems. By bridging computer-generated CAD models with real-time operational technology (OT) data, immersive displays enable intuitive monitoring, rapid diagnostics, and safer maintenance across complex processing facilities.

Read more
Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Master Acceptance Testing: Understanding FAT and SAT in Industrial Control Systems

Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) serve as critical quality assurance gateways in complex industrial control systems. Both procedures verify that programmable logic controllers (PLCs), distributed control systems (DCS), and associated field devices meet strict functional specifications. However, executing these tests effectively requires clear delineation between off-site staging and final field commissioning.

Read more