Product Description

The Ovation High-Performance Analog Input Module, model 5X00106G01, is designed to support HART-enabled communication within distributed control systems. This unit provides eight galvanically isolated analog input channels, each equipped with dedicated transceivers and optically isolated communication paths. By integrating with UARTs, the module ensures efficient and reliable HART data exchange, making it a robust solution for advanced process automation.

Technical Specifications

  • Manufacturer: Ovation

  • Model / Part Number: 5X00106G01

  • Category: PLCs / Machine Control

  • Subcategory: Analog Input Module

  • Channels: 8 galvanically isolated analog inputs

  • Input Range: 2.5–25 mA with under-range and over-range detection

  • A/D Resolution: 14-bit

  • Reference Accuracy (25°C): ±0.19% of full scale (20 mA) at 99.79% confidence

  • Accuracy Over Temperature: ±0.24% of full scale (20 mA) across full operating range

  • Sampling Rate:

    • 20 samples/sec with 60 Hz rejection

    • 25 samples/sec with 50 Hz rejection

  • Dielectric Isolation:

    • Channel-to-channel: 1000 VAC/VDC for 1 minute

    • Channel-to-logic: 1000 VAC/VDC for 1 minute

  • Operating Temperature: 0°C to +60°C (32°F to 140°F)

  • Humidity: 0%–95% non-condensing

  • Power Consumption:

    • Main: 4.1 W typical, 4.5 W maximum

    • Auxiliary: 3.84 W typical (20 mA × 8 loops × 24 V)

    • Module Dissipation: 5.06 W typical (EMOD + PMOD)

Application Scenarios

  • Designed for Ovation distributed control systems requiring HART-enabled analog input.

  • Ideal for process industries such as oil & gas, chemical, and power generation.

  • Provides accurate signal acquisition and diagnostics for monitoring field devices.

FAQ

Q: How many channels are supported?  A: The 5X00106G01 supports eight galvanically isolated analog input channels.

Q: What makes this module suitable for HART communication?  A: Each channel includes a dedicated transceiver with optically isolated communication to a UART, maximizing HART efficiency.

Q: What is the accuracy of this module?  A: At 25°C, accuracy is ±0.19% of full scale, with ±0.24% maintained across the full operating temperature range.

Q: How does this compare to non-HART analog input modules?  A: Unlike standard analog modules, the 5X00106G01 supports HART communication, enabling advanced diagnostics and device integration.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Optimizing Tank Level Control Using Proportional Algorithms in PLC Systems

Optimizing Tank Level Control Using Proportional Algorithms in PLC Systems

Industrial automation engineers frequently encounter liquid level regulation challenges across diverse process plants. Traditional ON-OFF control mechanisms often disrupt system stability due to abrupt actuator switching. Therefore, upgrading to closed-loop architectures like proportional control yields smoother responses. In a typical PLC environment, such as Siemens TIA Portal, engineers utilize closed-loop feedback to minimize process errors without requiring full PID complexity.

Read more
Understanding Why Your PLC Enters Stop Mode: Causes and Troubleshooting

Understanding Why Your PLC Enters Stop Mode: Causes and Troubleshooting

In industrial automation, programmable logic controllers (PLCs) serve as the core intelligence of modern factory automation and distributed control systems (DCS). Understanding how a PLC transitions between modes is vital for maintenance engineers. Typically, a PLC operates across four primary modes: Run, Stop, Start-Up, and Hold. When power is applied, the system immediately boots into Stop mode before initiating the Start-Up sequence. If the controller encounters a critical error during execution, it automatically reverts to Stop mode to prevent equipment damage. Therefore, monitoring these state transitions helps technicians maintain high system availability.

Read more
Comprehensive Guide to Servo Motor Drive Control Techniques in Industrial Automation

Comprehensive Guide to Servo Motor Drive Control Techniques in Industrial Automation

Precision motion control systems drive high-throughput manufacturing across modern industrial automation environments. Unlike standard induction motors running on basic variable frequency drives, servo motor systems deliver sub-millimeter positioning accuracy and fast dynamic response.

Read more