Skip to content

What are you looking for?


You may also like

Emerson VE5010 Intrinsically Safe Power Supply CarrierEmerson VE5010 Intrinsically Safe Power Supply CarrierEmerson VE5010 Intrinsically Safe Power Supply Carrier
Emerson VE5010 Intrinsically Safe Power Supply Carrier
Emerson VE5010 Intrinsically Safe Power Supply Carrier
Emerson VE5010 Intrinsically Safe Power Supply Carrier

Emerson VE5010 Intrinsically Safe Power Supply Carrier


Only 10 left - Selling fast

PRODUCT SKU : VE5010

PRODUCT TYPE : Power Supply Module

PRODUCT VENDOR : EMERSON


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for power distribution and signal isolation in DeltaV I/O subsystems, the Emerson VE5010 (VE5010, also cataloged as KJ4101X1-BC1) provides direct physical/electrical execution of intrinsically safe power regulation for hazardous area instrumentation.

Hardware Specifications

Parameter Specification
Model VE5010
Brand Emerson
Origin USA
Weight 0.82 kg (1.8 lbs)
Dimensions 93 mm x 168 mm x 35 mm
Operating Temp Not specified
Power Consumption Passive distribution
Input Rating 24 VDC
Function IS Power Supply Carrier

Process Control: Intrinsic Safety (Ex i) Barriers

The VE5010 carrier serves as a foundational component for implementing intrinsic safety within the DeltaV architecture. It facilitates the distribution of power to connected I/O modules while maintaining stringent energy-limiting barriers that prevent ignition-capable electrical or thermal energy from entering hazardous areas. The carrier is engineered to support Ex i compliance, ensuring that field-side circuits are galvanically isolated from the non-hazardous control bus. This implementation requires meticulous adherence to loop-drawing specifications and cable capacitance/inductance limits to maintain the safety integrity of the installed field instruments.

Frequently Asked Questions (FAQ)

Q: Can the VE5010 be used for non-intrinsically safe I/O modules?

A: The VE5010 is specifically designed for use with intrinsically safe DeltaV I/O modules. Use with non-IS modules will negate the intended safety protection and may result in improper module operation or damage to the carrier backplane.

Q: What is the recommended mounting configuration?

A: The module supports DIN-rail or panel mounting. Ensure that the mounting surface is grounded and that the module is installed in an environment free from excessive vibration, which could compromise the electrical contact between the module and the carrier backplane pins.

Field Installation Guidelines

  • Mounting: Secure the carrier to the DIN rail or panel using appropriate fastening hardware. Maintain adequate spacing between the VE5010 and non-IS components to prevent unintended coupling or mechanical interference.

  • Wiring: Terminate 24 VDC input power at the carrier power terminals. All field wiring must be routed according to local hazardous area installation codes, strictly segregating IS and non-IS circuits to prevent cross-talk or short-circuit failures.

  • Grounding: Bond the carrier chassis to the system earth ground. A low-impedance ground path is mandatory to ensure the stability of the safety barriers and to suppress electromagnetic noise that could interfere with signal precision.

  • Verification: After installation, measure the output voltage at the module connection points to ensure proper power delivery. Conduct a continuity test on all field loops to verify isolation from ground and ensure that field device capacitance and inductance parameters conform to the system safety design.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why 24V DC Power Supplies Standardize Modern Industrial Automation

Why 24V DC Power Supplies Standardize Modern Industrial Automation

Industrial control cabinets worldwide rely on 24V DC as the universal power standard for field instrumentation, sensors, and controllers. Walk into any manufacturing plant, and you will find PLCs, human-machine interfaces (HMIs), and smart actuators running on extra-low voltage DC. Standardizing on 24V DC enhances operational safety, lowers cabinet footprint, and maintains steady control performance across factory networks.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
Mastering Modern Industrial Joystick Controls in Heavy Automation

Mastering Modern Industrial Joystick Controls in Heavy Automation

Industrial joysticks play a pivotal role in human-machine interaction across heavy material handling and mobile hydraulics. These tactile controllers translate complex operator movements into precise electrical signals for PLCs, motion controllers, and DCS networks. Consequently, selecting and installing the right joystick architecture ensures operator safety, reduces fatigue, and optimizes equipment performance.

Read more