Skip to content

What are you looking for?


You may also like

Schneider Electric 140CPU11302 Modicon Quantum Controller Processor ModuleSchneider Electric 140CPU11302 Modicon Quantum Controller Processor ModuleSchneider Electric 140CPU11302 Modicon Quantum Controller Processor Module
Schneider Electric 140CPU11302 Modicon Quantum Controller Processor Module
Schneider Electric 140CPU11302 Modicon Quantum Controller Processor Module
Schneider Electric 140CPU11302 Modicon Quantum Controller Processor Module

Schneider Electric 140CPU11302 Modicon Quantum Controller Processor Module


Only 10 left - Selling fast

PRODUCT SKU : 140CPU11302

PRODUCT TYPE : Processor Module

PRODUCT VENDOR : Schneider


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Overview

The Schneider Electric 140CPU11302 executes primary logic calculation, communication orchestration, and system diagnostics within the Modicon Quantum automation platform. This standard-format central processing unit utilizes a dedicated 20 MHz 80186 micro-architecture to coordinate real-time machine execution and continuous process loop control. By integrating native Modbus and Modbus Plus communication paths, this controller module serves as the primary intelligence hub for critical utility control, water treatment plants, and manufacturing lines running ProWORX 32 or Concept programming environments.

Technical Specifications

Parameter Technical Specification Value
Manufacturer Schneider Electric
Model 140CPU11302
Range of Product Modicon Quantum Automation Platform
Product Type Central Processing Unit (Processor)
Condition 100% Brand New Original
Core Microprocessor 80186 clocked at 20 MHz (Without math coprocessor)
On-Board Memory Capacity 109 kB Internal RAM
Logic Execution Performance 0.3 to 1.4 ms per 1 Kinstruction (LL984)
Watchdog Timer Threshold 250 ms
Real-Time Clock Drift +/- 8 seconds per day within 32…140 °F (0…60 °C)
Local I/O Capacity 64 Input Words / 64 Output Words maximum
Remote I/O Capability 64 Input / 64 Output Words across 31 remote drops
Distributed Network Capacity 500 Input / 500 Output Words across 63 drops
Network Interfaces

1 x Modbus RS232 port


1 x Modbus Plus port

Maximum Network Expansion 2 Remote networks / 3 Distributed networks
Coprocessor Support Capacity Supports up to 2 network modules (NOM, NOE, CR, NMS)
Memory Retention Battery Lithium battery, 1.2 Ah capacity, 10-year service life
Backplane Current Demand 780 mA Bus current requirement
Product Net Weight 0.7 lb (0.3 kg)

Engineering Advantages

  • Native Dual-Network Communication Topology: Multi-device industrial plants require concurrent local diagnostic and high-speed peer-to-peer networking. The 140CPU11302 integrates one dedicated Modbus RS232 port alongside a high-performance Modbus Plus port directly on the front face. This hardware arrangement allows engineers to program or collect local HMI data via RS232 while the Modbus Plus interface drives deterministic, real-time data exchange across distributed controller nodes.

  • Highly Scalable Distributed I/O Mapping: Expansive industrial facilities demand large-scale sensor aggregation over wide physical areas. This processor accommodates complex topologies by managing up to 31 remote I/O drops over 2 distinct remote networks. Furthermore, it controls up to 63 distributed drops over 3 distributed networks, handling up to 500 input and 500 output words per network to support massive field device grids.

  • Deterministic Logic Execution Engine: High-speed packaging and critical tripping applications depend on highly predictable software scan times. Running the proven LL984 instruction set, this 20 MHz processor solves 1,000 instructions in 0.3 to 1.4 milliseconds. A hardware-enforced 250 ms watchdog timer monitors the core scan loop, immediately forcing safe fallback actions if a logic fault stalls the operating software.

  • Decoupled Communication Coprocessing: Intensive Ethernet or network traffic can degrade a primary CPU's logic processing speed. The 140CPU11302 architecture supports the addition of up to two specialized option modules, such as Network Option Modules (NOM) or Network Ethernet Modules (NOE). These cards offload communication stack processing from the main 80186 chip, keeping logic execution times rock-solid.

  • Decade-Long Non-Volatile Data Retention: Sudden facility power outages risk the loss of volatile recipe data and active register registers. This unit utilizes a high-capacity 1.2 Ah lithium battery combined with an ultra-low power consumption circuit (5 to 110 µA current draw). This system retains critical user application programs and configuration data inside the internal 109 kB RAM for up to 10 years without main backplane power.

FAQs

  • Is this 140CPU11302 processor module a brand new original unit?

    Yes. We supply this product strictly as a 100% brand new, original factory-sealed module. It arrives in the original Schneider Electric packaging with all authentic corporate branding, factory bar codes, and quality assurance seals completely intact.

  • Which legacy programming software packages support this Quantum CPU?

    This processor module fully integrates with Schneider Electric legacy development environments, specifically Modicon Concept and ProWORX 32 software. It utilizes the standard LL984 logic execution structure for direct compatibility with existing application files.

  • Does this specific hardware version contain an integrated key switch?

    No. The 140CPU11302 features the standard front-panel format without a mechanical security key switch. Engineers control software lockouts, online logic changes, and memory protection parameters via software commands inside the programming environment.

  • What are the primary precautions regarding the real-time clock performance?

    The internal real-time clock exhibits a maximum drift of +/- 8 seconds per day across its full operating temperature window of 32°F to 140°F (0°C to 60°C). For applications requiring precise sequence-of-events recording across multiple racks, we recommend implementing external network time synchronization via an attached Ethernet coprocessor module.

 

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Understanding Marshalling Cabinets in Industrial Control Systems Architecture

Understanding Marshalling Cabinets in Industrial Control Systems Architecture

Industrial control system deployments rely on structured signal distribution to bridge field instrumentation with central processing hardware. A marshalling cabinet serves as the vital intermediate connection point between heavy field home-run multi-pair cables and delicate input/output (I/O) modules housed inside Programmable Logic Controller (PLC) or Distributed Control System (DCS) enclosures. By segregating field cable terminations from control hardware, engineers maintain system flexibility, safeguard controller components, and streamline commissioning workflows.

Read more
FAT vs SAT in Industrial Control Systems: Key Differences and Execution Guide

FAT vs SAT in Industrial Control Systems: Key Differences and Execution Guide

Industrial control system deployment relies on strict verification protocols to guarantee operational safety, system stability, and regulatory compliance. Commissioning complex Programmable Logic Controller (PLC) racks, Distributed Control Systems (DCS), and Safety Instrumented Systems (SIS) requires two critical milestones: the Factory Acceptance Test (FAT) and the Site Acceptance Test (SAT). Both procedures validate that system automation meets design specifications, but they occur at different stages of project execution and target distinct operational risks.

Read more
Hub vs Switch vs Router in Industrial Automation Architecture

Hub vs Switch vs Router in Industrial Automation Architecture

Modern factory automation relies on reliable industrial networking infrastructure to exchange real-time field data across operational technology systems. Engineers often encounter networking hardware like hubs, switches, and routers when integrating Programmable Logic Controllers, Distributed Control Systems, and SCADA monitoring nodes. Although these devices share physical ports, they operate at different layers of the Open Systems Interconnection reference model and deliver distinct traffic management capabilities.

Read more