Skip to content

What are you looking for?


You may also like

GE DS200DTBAG1A Digital Contact Terminal BoardGE DS200DTBAG1A Digital Contact Terminal BoardGE DS200DTBAG1A Digital Contact Terminal Board
GE DS200DTBAG1A Digital Contact Terminal Board
GE DS200DTBAG1A Digital Contact Terminal Board
GE DS200DTBAG1A Digital Contact Terminal Board

GE DS200DTBAG1A Digital Contact Terminal Board


Only 10 left - Selling fast

PRODUCT SKU : DS200DTBAG1A

PRODUCT TYPE : Digital I/O Cards

PRODUCT VENDOR : General Electric


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Configured for high-speed contact signal acquisition in Mark V LM control systems, the GE DS200DTBAG1A (DS200DTBA Digital Contact Terminal Board) provides direct physical execution of 125 VDC or 24 VDC contact interrogation and signal routing to TCDA processing cores.

Hardware Specifications

Parameter Specification
Model DS200DTBAG1A
Brand General Electric
Origin USA
Operating Temp Standard industrial range
Power Consumption N/A (Distribution unit)
Interrogation Voltage 125 VDC or 24 VDC (Factory configured)
Input Capacity 46 contact inputs per core

Industrial Control and Firmware Flash Compatibility

The DS200DTBAG1A functions as a deterministic interface board for digital contact inputs in Q11, Q21, and Q51 core locations. To maintain signal integrity, the board provides optical isolation at the TCDA interface, ensuring that field-side transients do not propagate to the control logic. The CPU on the associated TCDA board performs status monitoring with a 1 ms resolution time stamp for state changes. While the board itself is a passive termination component lacking firmware flash compatibility, its operation is dictated by physical jumper configurations that set interrogation voltage and isolate field grounds. I/O density scaling is achieved through eight-contact input groupings, allowing for precise mapping of contact sense inversion within the TCDA I/O configuration.

Frequently Asked Questions

Q: Can the interrogation voltage be changed from 125 VDC to 24 VDC in the field?

A: No. The excitation voltage option is factory-set. Field adjustments to jumpers on the DTBA/DTBB boards are intended solely for isolating field grounds by cutting off interrogation voltage and must only be performed when the turbine is offline.

Q: How is a failure in the contact input circuit detected?

A: The Mark V LM controller performs continuous diagnostic checks on the input circuitry. If a circuit failure is detected, the system triggers an internal alert to the operator interface.

Field Installation Guidelines

  1. Ensure the Mark V LM system is fully de-energized and verified via lockout/tagout (LOTO) procedures before accessing the terminal board or modifying jumper configurations.
  2. Verify that input configuration (125 VDC vs 24 VDC) matches the field device specifications to prevent damage to the optical isolators on the TCDA board.
  3. Handle the module by the edges and use ESD-protected tools to prevent damage to the sensitive input groupings.
  4. When isolating field grounds via jumpers, ensure the turbine is completely stationary; any adjustments to these jumpers during active operation may result in loss of input monitoring and subsequent system trips.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why 24V DC Power Supplies Standardize Modern Industrial Automation

Why 24V DC Power Supplies Standardize Modern Industrial Automation

Industrial control cabinets worldwide rely on 24V DC as the universal power standard for field instrumentation, sensors, and controllers. Walk into any manufacturing plant, and you will find PLCs, human-machine interfaces (HMIs), and smart actuators running on extra-low voltage DC. Standardizing on 24V DC enhances operational safety, lowers cabinet footprint, and maintains steady control performance across factory networks.

Read more
Essential Motion Control Commands: A Practical Guide for Engineers

Essential Motion Control Commands: A Practical Guide for Engineers

Automation engineers often rely on precise position and speed control to drive modern factory machinery. Modern industrial systems, such as Programmable Logic Controllers (PLCs) and Distributed Control Systems (DCS), depend heavily on standardized motion instructions. Mastering these commands ensures operational safety, protects mechanical components, and optimizes cycle times across production lines.

Read more
Mastering Modern Industrial Joystick Controls in Heavy Automation

Mastering Modern Industrial Joystick Controls in Heavy Automation

Industrial joysticks play a pivotal role in human-machine interaction across heavy material handling and mobile hydraulics. These tactile controllers translate complex operator movements into precise electrical signals for PLCs, motion controllers, and DCS networks. Consequently, selecting and installing the right joystick architecture ensures operator safety, reduces fatigue, and optimizes equipment performance.

Read more