Skip to content

What are you looking for?


You may also like

Bently Nevada 3500/05-01-01-00-00-00 System RackBently Nevada 3500/05-01-01-00-00-00 System RackBently Nevada 3500/05-01-01-00-00-00 System Rack
Bently Nevada 3500/05-01-01-00-00-00 System Rack
Bently Nevada 3500/05-01-01-00-00-00 System Rack
Bently Nevada 3500/05-01-01-00-00-00 System Rack

Bently Nevada 3500/05-01-01-00-00-00 System Rack


Only 10 left - Selling fast

PRODUCT SKU : 3500/05/01-01-00-00-00

PRODUCT TYPE : System Racks

PRODUCT VENDOR : Bently Nevada


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Bently Nevada 3500/05-01-01-00-00-00, also cataloged as the 3500/05 System Rack, operates as a dedicated hardware component for physical module mounting and backplane bus signal routing within 3500 Series Machinery Protection System platforms.

Suffix Breakdown & Model Matrix

Option Field Code Configuration Detail
Rack Size 01 19-inch rack mount (16 slots)
Mounting Options 01 19-inch EIA rack mounting format
Agency Approval Option 00 None / Standard non-certified configuration
Reserved Option 1 00 Unassigned / Standard default
Reserved Option 2 00 Unassigned / Standard default

Hardware Specifications

Parameter Specification
Model 3500/05-01-01-00-00-00
Brand Bently Nevada
Origin USA
Weight 4.54 kg (10.00 lbs)
Dimensions Standard 19-inch EIA rack width, 16-slot capacity
Operating Temp -30 deg C to +65 deg C (-22 deg F to +149 deg F)
Power Consumption Passive chassis backplane structure
Bus Architecture High-speed internal backplane communications bus
Slot Density 16 module slots (Slot 0 reserved for Power Supply, Slot 1 for RIM)

Rotor Dynamics and Cross-Talk Suppression

The 3500/05 16-slot chassis provides high-density backplane signal pathways that route raw eddy-current probe voltage and dynamic vibration waveforms directly between monitor modules and keyphasor inputs. Integrated shielding plane geometry inside the multilayer backplane printed circuit board maintains cross-talk suppression between adjacent high-frequency dynamic channels. This signal integrity enables accurate rotor dynamics monitoring and gap voltage validation across full-scale machine monitoring operations.

Frequently Asked Questions

Q: Can modules be inserted or removed from the 3500/05 backplane while power is applied?

A: Yes, modules designed for the 3500 Series system support hot-swapping within the 3500/05 rack without interrupting operation of unaffected slots or causing backplane signal corruption.

Q: How is chassis grounding managed across the 16 slots of the 3500/05 chassis?

A: The rack frame features a central earth ground bonding stud on the rear enclosure to maintain equipotential reference across all installed card guides and signal shields.

Field Installation Guidelines

  1. Mount the 19-inch 3500/05 chassis into a standard EIA instrument rack using appropriate panel mounting hardware.
  2. Connect a dedicated heavy-gauge grounding conductor from the chassis earth ground stud on the rear of the rack to the main station ground bar.
  3. Ensure slot 0 is populated with a 3500 Power Supply module and slot 1 contains the Rack Interface Module (RIM) before installing monitoring cards.
  4. Insert monitor modules along card guides until the backplane connectors seat completely, then tighten upper and lower front-panel thumbscrews.
  5. Route dynamic signal wires away from high-voltage field wiring to prevent electromagnetic interference coupling into the backplane.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.