Configured for high-precision data acquisition in M1 automation platforms, the Bachmann AI204/2 (AI204/2 Analog Input Module) provides direct physical/electrical execution of two-channel voltage measurement with sub-millisecond sampling capabilities.

Hardware Specifications

Parameter Specification
Model AI204/2
Brand Bachmann
Origin Austria
Weight 0.28 kg
Dimensions 102 mm x 12 mm x 130 mm
Operating Temp 0 deg C to 60 deg C
Power Consumption 2.5 W
Input Channels 2
Input Range ±10 V
Resolution 16-bit
Sampling Time 20 μs

Profinet / EtherNet/IP Deterministic Networks

The AI204/2 integrates into the M1 backplane to facilitate deterministic network connectivity between field sensors and the controller. The module's architecture is optimized for backplane bus communication velocity, ensuring that high-speed data streams—sampled at 20 μs—are processed without jitter. I/O density scaling is supported through the module's small form factor, allowing for multiple high-speed analog inputs to be deployed within a single rack. Firmware flash compatibility is maintained, ensuring that digital averaging algorithms and the signal processing stack remain compliant with the latest controller firmware revisions.

Frequently Asked Questions

Q: Can the channels be operated as non-isolated inputs?

A: The AI204/2 features single isolation for each channel, providing protection against ground loops between connected analog sources. Ensure all source commons are verified against the module's reference potential.

Q: How does the digital averaging function affect the output latency?

A: Digital averaging improves the signal-to-noise ratio by processing multiple samples; however, this creates a trade-off with group delay. Users should tune the averaging depth to match the process loop bandwidth requirements.

Q: Is the ±10 V range fixed or software-scalable?

A: The input stage is calibrated for a ±10 V range at 16-bit resolution. Scaling and normalization are performed in the software application layer, allowing for the mapping of raw counts to engineering units.

Field Installation Guidelines

  1. Shielding: Connect cable shields to the cabinet functional earth (FE) using low-impedance clamps as close to the module as possible to maximize noise immunity.
  2. Signal Integrity: Given the 20 μs sampling time, maintain minimal wire lengths and use twisted-pair cabling to minimize susceptibility to radiated electromagnetic interference.
  3. Common Mode: Although the module is isolated, ensure that the common-mode voltage between the two channels does not exceed the specified safety limits defined for the input stage.
  4. Connector Seating: Ensure the terminal block is securely locked into the module housing to prevent intermittent contact resistance, which can cause significant measurement errors in high-precision (0.005%) circuits.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more