Skip to content

What are you looking for?


You may also like

R7140L1009/U | Honeywell | Burner Control ModuleR7140L1009/U | Honeywell | Burner Control ModuleR7140L1009/U | Honeywell | Burner Control Module
R7140L1009/U | Honeywell | Burner Control Module
R7140L1009/U | Honeywell | Burner Control Module
R7140L1009/U | Honeywell | Burner Control Module

R7140L1009/U | Honeywell | Burner Control Module


Only 10 left - Selling fast

PRODUCT SKU : R7140L1009/U

PRODUCT TYPE : Burner Control Modules

PRODUCT VENDOR : Honeywell


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Honeywell R7140L1009/U, also cataloged as the R7140L1009/U Burner Control Module, operates as a dedicated hardware component for automatic burner sequencing, flame supervision, and diagnostic execution within 7800 Series burner management systems.

Hardware Specifications

Parameter Specification
Model R7140L1009/U
Brand Honeywell
Origin USA
Weight 1.4 kg (3 lbs 1 oz)
Dimensions 177 mm x 156 mm x 146 mm (7 in. x 6 5/32 in. x 5 3/4 in.)
Operating Temp -40 to +60 deg C (-40 to +140 deg F)
Power Consumption 120 VAC (+10, -15%), 50/60 Hz (+/-10%)
Application Type Upgrade replacement programming control for R4140 and BC7000
PrePurge Timing Determined by ST7800 Plug-in Purge Timer Card
PostPurge Timing 15 sec
Pilot Flame Establishing Period 4 sec or 10 sec
Main Flame Establishing Period 10 sec or 15 sec
Early Spark Termination 5 sec
Interlocks / Airflow Check Lockout / User selectable
Required Accessories ST7800 Purge Timer Card, R78XX Series Amplifier Module
Vibration / Compliance 0.5 G environment / UL Recognized File MP268, FCC Part 15 Class B

Cold Junction Compensation and Channel-to-Channel Isolation

The module incorporates microprocessor-based signal processing circuitry designed to interface directly with specialized R78XX flame signal amplifiers and ST7800 purge timing cards. Internal optical isolation channels decouple line-voltage interlock input circuits from sensitive digital timing logic, preventing high-voltage electrical noise from corrupting flame safety sequencing. Embedded 4-20 mA HART feedback capabilities and cold junction reference logic in connected flame sensors enable precise monitoring of flame signal amplitude across front panel diagnostic interfaces.

Frequently Asked Questions

Q: What additional components are required to install the R7140L1009/U module as a replacement control?

A: The module requires an ST7800 Plug-in Purge Timer Card (to set prepurge timing) and a compatible R78XX Series Flame Signal Amplifier (such as R7847, R7848, R7849, or R7861).

Q: Can the R7140L1009/U directly replace legacy Honeywell BC7000 and R4140 programmer controls?

A: Yes, it is engineered as an upgrade replacement control specifically for legacy BC7000 and R4140 burner programmer chassis installations.

Field Installation Guidelines

  1. Ensure main 120 VAC electrical power to the burner control panel is completely de-energized prior to removing or mounting the control module.
  2. Plug the ST7800 Purge Timer Card and appropriate R78XX Flame Signal Amplifier into their respective card slots on the R7140L1009/U unit before mounting.
  3. Align the subbase mounting feet and secure the module onto the wiring subbase using captive mounting screws.
  4. Verify that field wiring connections for interlocks, airflow switch, pilot valve, and main valve adhere strictly to local electrical and safety code requirements.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Comparing PID and Model Predictive Control (MPC) in Industrial Automation

Comparing PID and Model Predictive Control (MPC) in Industrial Automation

Advanced process control strategies remain fundamental for maintaining optimal plant efficiency and product quality. Therefore, control engineers frequently evaluate whether a traditional Proportional-Integral-Derivative (PID) algorithm or a Model Predictive Control (MPC) strategy suits a given application. In my 15 years of commissioning distributed control systems (DCS) and factory automation networks, I have tuned thousands of PID loops while deploying complex MPC packages on multivariable distillation columns. Below, I break down the core operational differences between these two foundational control methodologies.

Read more
Mastering Time Synchronization in Industrial Automation Applications

Mastering Time Synchronization in Industrial Automation Applications

Precise time synchronization remains vital for modern industrial automation, distributed control systems (DCS), and power protection networks. Therefore, control engineers must maintain uniform clocks across all controllers, human-machine interfaces (HMIs), and supervisory stations. In my 15 years of commissioning complex industrial automation projects, I have frequently investigated root-cause failures where misaligned timestamps obscured the true sequence of events. Below, I break down the core time synchronization protocols and methods essential for reliable factory automation.

Read more
Designing Robust SCADA Systems for Electrical Substation Automation

Designing Robust SCADA Systems for Electrical Substation Automation

Electrical substation automation requires rigorous engineering standards to guarantee uninterrupted power distribution and grid stability. Therefore, control engineers must design supervisory control and data acquisition (SCADA) architectures with absolute precision. In my 15 years of commissioning power protection and substation automation systems, I have witnessed how meticulous SCADA design prevents catastrophic grid failures. Below, I outline the critical engineering practices required to build reliable substation SCADA solutions.

Read more