Product Details

Configured for power conversion and interface regulation in GE EX2000 Excitation Control Systems, the GE DS200PCCAG6A (DS200PCCA Power Connect Card) provides direct physical execution of drive-to-SCR bridge signal transmission and transient suppression.

Hardware Specifications

Parameter Specification
Model DS200PCCAG6A
Brand General Electric
Origin USA
Weight 1.5 kg
Dimensions 160 x 100 x 50 mm
Operating Temp -20 deg C to 70 deg C
Power Consumption 200 W
Input Voltage 24 VDC
Output Voltage 12 VDC
Output Ripple 100 mV peak-to-peak
Mounting DIN Rail

Industrial Control and Firmware Flash Compatibility

The DS200PCCAG6A utilizes pulse transformer coupling to manage gate drive delivery between the excitation control circuitry and the SCR power bridge, ensuring galvanic isolation. The module supports I2C and digital PWM control interfaces for real-time regulation. While the board is factory-configured for specific power stages, its backplane bus communication velocity and logic execution remain fixed. For low-to-medium horsepower applications, the board incorporates onboard snubber circuits to mitigate transient surges across AC lines and DC buses. In high-horsepower configurations, these circuits may be relocated external to the PCCA board to manage increased thermal dissipation profiles and electrical stress. Firmware flash compatibility is not supported for this hardware-defined interface card.

Frequently Asked Questions

Q: Can the onboard snubber circuits be bypassed for high-horsepower applications?

A: In high-horsepower systems, snubber circuits are typically relocated off-board to manage thermal dissipation. Attempting to force high-stress operation through the onboard components may exceed their design limits.

Q: Are there user-configurable settings on the PCCAG6A card?

A: No. All signal timing and gate drive parameters are determined by the drive control software and the physical layout of the SCR bridge. The card functions as a signal transmission and protection interface without field-adjustable logic.

Field Installation Guidelines

  1. Ensure the EX2000 cabinet is de-energized and DC bus capacitors are fully discharged before mounting the card onto the DIN rail.
  2. Verify that the 24 VDC input supply is regulated and within specified tolerances to ensure a stable 12 VDC output and nominal 100 mV peak-to-peak ripple.
  3. Secure all pulse transformer leads to the SCR gate terminals, ensuring correct phasing to prevent misfiring of the power bridge.
  4. If installing in a high-horsepower system, verify that all external snubber circuit connections have been correctly rerouted according to the specific excitation system schematic.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Essential SCADA Features for Modern IoT-Enabled Industrial Automation

Essential SCADA Features for Modern IoT-Enabled Industrial Automation

The convergence of traditional SCADA systems with the Industrial Internet of Things (IIoT) has redefined factory automation. Choosing a robust platform requires more than just standard monitoring capabilities. In this era of Industry 4.0, your supervisory system must bridge the gap between legacy control systems and enterprise-level data integration.

Read more
Selecting Rockwell Automation Allen-Bradley PLCs for Small and Mid-Sized Applications

Selecting Rockwell Automation Allen-Bradley PLCs for Small and Mid-Sized Applications

Rockwell Automation remains a cornerstone in global industrial automation. Their Allen-Bradley brand provides a comprehensive portfolio of control systems designed to meet diverse production requirements. Choosing the right programmable logic controller (PLC) is critical for system reliability and scalability. This guide analyzes the Micro and Compact Logix families to help you select the optimal solution for small and medium-scale projects.

Read more
Strategic Selection: Choosing the Right SCADA Software for Your PLC Project

Strategic Selection: Choosing the Right SCADA Software for Your PLC Project

In industrial automation, the SCADA (Supervisory Control and Data Acquisition) system acts as the bridge between raw machine data and actionable human intelligence. Selecting the incorrect software platform can lead to integration bottlenecks, scalability issues, and excessive long-term maintenance costs. As an automation consultant with 15 years of experience, I have guided many projects through the selection process. Below are the essential criteria for choosing a platform that ensures both performance and longevity.

Read more