PRODUCT SKU : DC532 1SAP240100R0001

PRODUCT TYPE : Digital Input/Output Modules

PRODUCT VENDOR : ABB


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The ABB 1SAP240100R0001, also cataloged as the DC532 Digital Input/Output Module, operates as a dedicated hardware component for discrete signal monitoring and field actuation within ABB AC500 platforms. Configured with 16 dedicated 24 VDC digital inputs and 16 configurable 24 VDC 0.5 A digital inputs/outputs, this S500 platform extension unit provides direct electrical signal acquisition and transistor-based switching execution.

Hardware Specifications

Parameter Specification
Model DC532
Product ID 1SAP240100R0001
Brand ABB
Product Type Digital Input/Output Modules
System Platform ABB AC500 / S500 I/O System
Dedicated Digital Inputs 16 channels (24 VDC)
Configurable I/O Channels 16 channels (24 VDC, 0.5 A)
Input Voltage Range 0 to 30 V DC
Input Current 5 mA
Output Type Transistor
Output Current Rating 0.5 A
Supply Voltage 20.4 to 28.8 V DC
Signal Exchange Delay 0.1 to 32 ms
Wiring Architecture 1-wire connection
Ingress Protection IP20
Dimensions 67.5 mm x 76 mm x 62 mm
Net Weight 0.114 kg
Operating Temp 0 to +60 deg C
Power Consumption 20.4 to 28.8 V DC terminal supply
Origin Germany

Backplane Bus Interfacing and Communication

The DC532 module interfaces directly with the S500 expansion bus to establish backplane bus communication velocity and deterministic network synchronization across local or distributed I/O racks. Multi-pin bus connectors integrated into the underlying terminal base pass high-density signal data directly to the host CPU processor. Firmware flash compatibility is governed automatically by the CPU master during bus scan cycles, maintaining deterministic IO processing times between 0.1 ms and 32 ms.

Frequently Asked Questions

Q: How are the 16 configurable channels on the DC532 module defined?

A: Channel modes are defined via software parameters in the central controller to operate either as 24 VDC digital inputs or as 24 VDC 0.5 A transistor outputs.

Q: Does the DC532 module require a specific terminal base unit for field wiring?

A: Yes. The module snaps onto a compatible S500 terminal base unit (such as TU515 or TU516) to establish 1-wire field circuit terminations and backplane connection.

Q: What protection level does the DC532 enclosure provide?

A: The module holds an IP20 protection rating and must be installed inside an IP54 or higher industrial enclosure to meet environmental site specifications.

Field Installation Guidelines

  1. Mount the matching S500 terminal base onto a 35 mm DIN rail, securing the grounding spring firmly against the metal rail.
  2. Align the DC532 module housing over the terminal base slot guide pins and press straight down until the locking mechanisms click into place.
  3. Route 24 VDC power supply lines to the designated L+ and M supply terminals on the base, keeping wiring lengths as short as practical.
  4. Connect 1-wire field sensor and actuator lines to the assigned terminal points, maintaining physical separation between high-voltage power cables and 24 VDC I/O lines.
  5. Apply power to the system bus and verify channel status LED indications before commissioning connected output devices.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Mastering Functional Safety Terminology in Industrial Automation

Mastering Functional Safety Terminology in Industrial Automation

In modern process control and factory automation, managing operational risk is a top engineering priority. High-speed machinery, high-pressure vessels, and continuous processes present constant hazards to personnel and equipment. Modern plant operations rely heavily on functional safety strategies to mitigate these risks. This guide breaks down the essential functional safety terminology that every control systems engineer should master.

Read more
Understanding Dry Contacts in PLC Wiring: An Industrial Automation Guide

Understanding Dry Contacts in PLC Wiring: An Industrial Automation Guide

Mastering contact switching principles is essential for reliable control panels. Field devices and PLCs interface through dry or wet contacts. This technical guide examines the mechanics of dry contacts, explores their wiring architectures, and evaluates their key advantages in industrial automation.

Read more
Ultimate Commissioning Checklist for Industrial Automation Systems: An Engineering Guide

Ultimate Commissioning Checklist for Industrial Automation Systems: An Engineering Guide

Commissioning is the most decisive phase of an industrial automation project, transforming control hardware and software into an operational facility. Thorough testing prevents costly startup delays and builds customer confidence. This guide covers essential checklists, electrical standards, and best practices.

Read more