Skip to content

What are you looking for?


You may also like

ABB UR600IR Mod.1000 Uvisor Flame Detection ProbeABB UR600IR Mod.1000 Uvisor Flame Detection ProbeABB UR600IR Mod.1000 Uvisor Flame Detection Probe
ABB UR600IR Mod.1000 Uvisor Flame Detection Probe
ABB UR600IR Mod.1000 Uvisor Flame Detection Probe
ABB UR600IR Mod.1000 Uvisor Flame Detection Probe

ABB UR600IR Mod.1000 Uvisor Flame Detection Probe


Only 10 left - Selling fast

PRODUCT SKU : UR600IR

PRODUCT TYPE : Flame Detection Probes

PRODUCT VENDOR : ABB


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The ABB UR600IR Mod.1000, also cataloged as the UR600IR Flame Detection Probe, operates as a dedicated hardware component for infrared radiation monitoring and flame quality evaluation within industrial boiler burner management systems (BMS). It monitors infrared flicker frequencies emitted by combustion flames to provide reliable flame disk detection and discrimination.

Hardware Specifications

Parameter Specification
Model UR600IR Mod.1000
Brand ABB
Origin Italy / Sweden
Weight 2.10 kg
Dimensions Standard Uvisor Industrial Probe Housing
Operating Temp -20 to +70 deg C
Power Consumption 24 VDC System Power Supply
Detection Spectrum Infrared (IR) flicker radiation
Target Applications Oil, gas, coal, and multi-fuel burner systems
Series Family ABB Uvisor Flame Monitoring Systems

Backplane Bus & I/O Isolation Profiles

The ABB UR600IR Mod.1000 flame detection probe utilizes optical sensing elements coupled with onboard pre-amplification to optimize signal-to-noise ratios across harsh furnace environments. The unit routes low-frequency flame flicker signals through narrow-band filtering electronics to prevent false discrimination from background thermal radiation and adjacent burner cross-talk. Isolated signal output channels interface with control room control modules (such as Uvisor central units) while integrated internal shielding limits electromagnetic interference along long field cable runs.

Frequently Asked Questions

Q: What primary spectrum does the UR600IR Mod.1000 utilize for flame detection?

A: The UR600IR Mod.1000 measures infrared (IR) flicker radiation emitted by combustion flames, making it suitable for gas, oil, and pulverized coal burners.

Q: How is thermal protection managed for the probe assembly near high-temperature burner fronts?

A: The housing relies on continuous cooling air purge delivered via the mounting assembly to maintain internal electronics within specified ambient operating temperature limits and keep optical elements clean.

Q: Can the UR600IR probe discriminate between target burner flames and background furnace radiation?

A: Yes, onboard electronic filtering analyzes dynamic flame flicker frequencies to distinguish active combustion from static hot refractory background radiation.

Field Installation Guidelines

  1. Ensure the burner management system is safely shut down and local power sources are isolated prior to installation.
  2. Mount the sight tube and swivelling head securely to the burner wall, verifying an unobstructed line of sight to the flame target zone.
  3. Connect continuous, clean, dry purge air to the cooling port before exposing the probe to furnace ambient heat.
  4. Terminate signal cables to the rear terminal block using shielded, twisted-pair cabling, anchoring the shield at a single ground point.
  5. Tighten all mechanical mounting hardware and threaded connections to ensure minimum 5-thread engagement before re-energizing the flame safety loop.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Transforming Shop Floor Data into Actionable Insights: A Deep Dive into MES

Manufacturing Execution Systems serve as the digital backbone of modern factory floors. Positioned at Level 3 of the ISA-95 automation pyramid, MES links enterprise resource planning with real-time shop floor control systems. Today, industrial operators rely on MES software to bridge operational strategy with physical production execution.

Read more
Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Managed Switch vs. Unmanaged Switch: Industrial Ethernet Architecture

Industrial Ethernet forms the backbone of factory automation. Selecting the right switch architecture determines system uptime, data throughput, and OT cyber resilience. This technical guide evaluates managed vs. unmanaged switches, analyzing operational differences, security controls, and selection criteria.
Read more
Hot Standby vs. Cold Standby Redundancy in Industrial Automation

Hot Standby vs. Cold Standby Redundancy in Industrial Automation

System availability determines process safety and productivity in industrial automation. Control engineers deploy redundancy to eliminate single points of failure. This technical guide evaluates Hot Standby vs. Cold Standby architectures, comparing failover speeds, memory sync, cost trade-offs, and field selection criteria.

Read more