Product Details
Configured for two-winding transformer differential protection, tap changer voltage regulation, and sub-station signal acquisition in Relion 620 series platforms, the ABB RET620 (RET620 Transformer Protection and Control Relay) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | RET620 |
| Brand | ABB |
| Origin | Finland |
| Operating Temp | -25 to +55 deg C |
| Power Consumption | Standard Relion 620 series internal power supply draw |
| Target Application | Two-winding power transformers, step-up transformers, generator-transformer blocks |
| Core Functions | Differential protection, automatic voltage regulation (OLTC), arc protection |
| Earth-Fault Schemes | High-impedance or numerical low-impedance restricted earth-fault (REF) |
| Communication Protocols | IEC 61850 Ed. 1 & Ed. 2 (GOOSE, IEC 61850-9-2 LE), Modbus, DNP3, IEC 60870-5-103 |
| Network Redundancy | High-availability Seamless Redundancy (HSR) and Parallel Redundancy Protocol (PRP) |
| Time Synchronization | IEEE 1588 v2 Precision Time Protocol (PTP) |
| User Interface | Large graphical LCD with customizable Single-Line Diagram (SLD) and web HMI |
Backplane Bus Communication Velocity & Deterministic Networks
The RET620 optimizes backplane bus communication velocity and internal analog-to-digital signal processing to execute high-speed transformer differential algorithms with inrush current stabilization. Integrated native IEC 61850 Edition 1 and Edition 2 protocol stacks support GOOSE messaging and IEC 61850-9-2 LE sampled values, minimizing hardwired interconnections across deterministic networks. Utilizing HSR and PRP redundant Ethernet architectures along with IEEE 1588 v2 Precision Time Protocol (PTP), the unit ensures uninterrupted data synchronization and firmware flash compatibility across utility and industrial substation automation networks.
Frequently Asked Questions
Q: What network redundancy standards are supported by the RET620 Ethernet interface?
A: The relay natively supports High-availability Seamless Redundancy (HSR) and Parallel Redundancy Protocol (PRP) to prevent communication loss in critical substation network loops.
Q: How is restricted earth-fault (REF) protection configured on this unit?
A: The RET620 supports various neutral earthing configurations matching either high-impedance or numerical low-impedance restricted earth-fault principles.
Q: What mechanical housing design is utilized for maintenance and testing?
A: The relay features a withdrawable plug-in unit design, allowing rapid physical isolation, testing, and replacement without disturbing rear field terminal wiring.
Field Installation Guidelines
- Cut out the switchgear panel door or mounting rack according to Relion 620 series dimensional templates, inserting the outer case frame into position.
- Connect the protective earthing conductor directly to the chassis ground screw using a heavy gauge copper braid before making any signal or power connections.
- Wire the current transformer (CT), voltage transformer (VT), and on-load tap changer (OLTC) control lines to the rear terminal blocks, ensuring correct phase polarity.
- Connect dual Ethernet communications cables to the RJ45/LC ports to establish HSR or PRP redundancy loops.
- Insert the withdrawable relay plug-in unit into the flush-mounted case until the locking handle latches securely, then apply auxiliary power and verify relay readiness via the local graphical display.
Additional Information
- 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
- 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
- 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
- Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
- Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
- Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.