The ABB CMA135 3DDE 300 415, also cataloged as the CMA135 Synpol D Module, operates as a dedicated hardware component for high-density HART signal multiplexing and field device integration within ABB S800 I/O systems.

Hardware Specifications

Parameter Specification
Model CMA135 (3DDE 300 415)
Brand ABB
Origin Sweden
Weight 0.7 kg
Dimensions 45 mm x 100 mm x 125 mm
Operating Temp -25 to +70 deg C
Power Consumption ~2.5 W (24 VDC via S800 I/O baseplate)
HART Channels 16 channels (multiplexed, HART 5, 6, 7 all revisions)
Isolation 1500 VAC (channel-to-channel and channel-to-system)
Communication Interface ABB internal S800 bus
Field Interface 2 x M12 connectors (8 HART pairs each)
Relative Humidity 5% to 95% (non-condensing)

Backplane Bus Communication Velocity and Firmware Flash Compatibility

The CMA135 module processes multiplexed HART variable polling without degrading backplane bus communication velocity across the host S800 I/O backplane. Hardware-level 1500 VAC channel isolation protects internal signal processing circuits from earth potential shifts and field-induced noise. Standardized firmware flash compatibility across ABB controller platforms ensures deterministic data updates and seamless I/O density scaling across distributed node configurations.

Frequently Asked Questions

Q: How is primary operating power supplied to the CMA135 module?

A: Power is drawn directly from the 24 VDC auxiliary bus embedded within the S800 I/O baseplate, consuming approximately 2.5 W during standard operation.

Q: What isolation rating exists between individual HART channels and the system logic?

A: Galvanic isolation rated at 1500 VAC is maintained channel-to-channel as well as between individual channels and the backplane logic interface.

Q: Are field connection points wired via standard terminal blocks or specialized connectors?

A: Signal wiring connects through two M12 field connectors, with each M12 interface accepting 8 twisted HART channel pairs.

Field Installation Guidelines

  1. Turn off 24 VDC baseplate power and verify system isolation prior to seating the CMA135 module.
  2. Wear an ESD wrist strap connected to cabinet frame earth ground during board handling.
  3. Align the module housing guide pins with the target slot on the S800 baseplate and push firmly until fully latched.
  4. Secure M12 field connector plugs onto the front panel receptacles, tightening retaining collars to ensure solid contact and IP-rated sealing.
  5. Apply power to the S800 baseplate and verify module boot status and HART channel communication LEDs via controller diagnostic software.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Voice-Activated Industrial Automation: Integrating Speech Control into PLC and DCS Architectures

Industrial automation integrates speech recognition, IIoT protocols, and NLP with PLCs and DCS to streamline operations. By leveraging advanced edge computing, engineers enable real-time, hands-free control—allowing personnel to manage smart factory processes safely away from hazardous equipment.

Read more
Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Modern Industrial Automation: Transforming Safety and Efficiency in Mining Operations

Industrial automation has evolved from a simple manufacturing tool into the operational backbone of high-risk sectors. Modern mining operations increasingly rely on advanced control systems, programmable logic controllers (PLCs), distributed control systems (DCS), and artificial intelligence to address deep-underground hazards. By replacing manual labor in high-risk zones, factory automation technologies protect personnel while significantly boosting operational throughput.

Read more
Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

Step-by-Step System Cabinet Health Check Guide for PLC and DCS Infrastructure

System cabinet health checks ensure long-term reliability in industrial automation. Preventative maintenance prevents hardware degradation, communication loss, and unplanned outages in control networks. This guide outlines the standard operating workflow for inspecting PLC and DCS cabinets to maintain peak performance.
Read more