ABB AX561 1TNE968902R1301 S500 Analog I/O ModuleABB AX561 1TNE968902R1301 S500 Analog I/O ModuleABB AX561 1TNE968902R1301 S500 Analog I/O Module
ABB AX561 1TNE968902R1301 S500 Analog I/O Module
ABB AX561 1TNE968902R1301 S500 Analog I/O Module
ABB AX561 1TNE968902R1301 S500 Analog I/O Module

ABB AX561 1TNE968902R1301 S500 Analog I/O Module


Only 10 left - Selling fast

PRODUCT SKU : AX561 1TNE968902R1301

PRODUCT TYPE : Analog Input/Output Modules

PRODUCT VENDOR : ABB


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The ABB AX561 1TNE968902R1301, also cataloged as the AX561 Analog Input/Output Module, operates as a dedicated hardware component for analog signal processing and field device control within ABB S500 and AC500-eCo I/O platforms. The module manages 4 analog inputs and 2 analog outputs configured for voltage or current loops using a 1-wire connection scheme. It converts incoming analog field variables into 12-bit digital values while driving proportional control signals to field actuators.

Hardware Specifications

Parameter Specification
Model AX561 1TNE968902R1301
Brand ABB
Origin Germany / China
Weight 0.122 kg (0.27 lbs) net / 0.225 kg gross
Dimensions 34 mm x 135 mm x 74 mm (1.34 in x 5.31 in x 2.91 in)
Operating Temp 0 to +60 deg C (Storage: -40 to +70 deg C)
Power Consumption Supplied via internal I/O bus and 24 VDC process power
Analog Inputs 4 channels (Voltage U, Current I, 12-bit resolution)
Analog Outputs 2 channels (Voltage U, Current I, 12-bit resolution)
Wiring Interface 1-wire connection, pluggable terminal blocks
Degree of Protection IP20 housing

Deterministic I/O Density Scaling and Firmware Flash Compatibility

The AX561 module scales analog I/O density within compact DIN-rail mounting footprints, executing continuous signal updates across the S500 expansion bus. Integrated firmware flash compatibility across AC500-eCo CPU processors ensures automatic parameter assignment during rack initialization. High-velocity backplane communication prevents data transmission latencies, maintaining deterministic execution for 12-bit conversion cycles on both input acquisition and output command channels.

Frequently Asked Questions

Q: What resolution is provided on the analog channels of the AX561 module?

A: Both the 4 analog inputs and the 2 analog outputs feature a 12-bit analog-to-digital / digital-to-analog signal conversion resolution.

Q: Can the AX561 channels be hot-swapped while the CPU is executing logic?

A: No. Power to the CPU terminal base and process voltage supply must be isolated prior to removing or seating the module to avoid bus communication faults and hardware damage.

Field Installation Guidelines

  1. Mount the AX561 onto the S500/AC500-eCo terminal base unit on a standard 35 mm DIN rail, pushing until the locking latch firmly clicks.
  2. Verify that all field wiring for voltage (U) or current (I) loops is de-energized before inserting conductors into the pluggable terminal blocks.
  3. Keep analog signal cables physically separated from high-voltage AC lines and switching inductive loads by a minimum distance of 200 mm.
  4. Ground all shielded twisted-pair cables at a single point near the panel entry point to eliminate potential ground loop interference across 12-bit resolution channels.
  5. Confirm that the terminal block screws are torqued to 0.5 Nm to maintain secure mechanical and electrical contact.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Will PLCs Become Obsolete? The Future of Control Systems in Industry 4.0

Will PLCs Become Obsolete? The Future of Control Systems in Industry 4.0

Modern manufacturing is undergoing a rapid technological transformation driven by Industry 4.0 innovations. Technologies like Artificial Intelligence (AI), Machine Learning (ML), and the Industrial Internet of Things (IIoT) are dominating discussions across the factory automation sector. Consequently, many engineers wonder if these advanced digital tools will eventually replace traditional Programmable Logic Controllers (PLCs). However, evaluating the core physics of industrial operations reveals a very different reality for control systems.

Read more
Demystifying Open Platform Communication (OPC): The Backbone of Industrial Interoperability

Demystifying Open Platform Communication (OPC): The Backbone of Industrial Interoperability

Interoperability remains a cornerstone requirement for modern smart factories and process automation. Open Platform Communication (OPC) bridges the gap between disparate hardware platforms, control systems, and visualization software. By establishing a universal communication standard, OPC allows field controllers, SCADA platforms, and enterprise software from different vendors to exchange real-time data seamlessly.

Read more
Understanding Siemens PLC Memory Cards: MMC, SMC, and SD Solutions in Industrial Automation

Understanding Siemens PLC Memory Cards: MMC, SMC, and SD Solutions in Industrial Automation

Memory management plays a pivotal role in maintaining control system reliability across modern manufacturing plants. Industrial control systems rely on specialized memory cards to store project logic, firmware updates, and retentive system data. Siemens uses several memory architectures, including Micro Memory Cards (MMC) and SIMATIC Memory Cards (SMC). Engineers must understand these hardware variations to ensure zero data loss and minimize downtime during maintenance routines.

Read more