AAI841-S50 | Yokogawa | CENTUM VP Analog I/O Module (8-Input / 8-Output)AAI841-S50 | Yokogawa | CENTUM VP Analog I/O Module (8-Input / 8-Output)AAI841-S50 | Yokogawa | CENTUM VP Analog I/O Module (8-Input / 8-Output)
AAI841-S50 | Yokogawa | CENTUM VP Analog I/O Module (8-Input / 8-Output)
AAI841-S50 | Yokogawa | CENTUM VP Analog I/O Module (8-Input / 8-Output)
AAI841-S50 | Yokogawa | CENTUM VP Analog I/O Module (8-Input / 8-Output)

AAI841-S50 | Yokogawa | CENTUM VP Analog I/O Module (8-Input / 8-Output)


Only 10 left - Selling fast

PRODUCT SKU : AAI841-S50

PRODUCT TYPE : Analog I/O Module

PRODUCT VENDOR : Yokogawa


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Technical Overview

The AAI841-S50 is a versatile analog mixing module designed for the Yokogawa CENTUM VP integrated control system. This module is engineered to handle both data acquisition and signal output within a single hardware footprint, featuring 8 input channels and 8 output channels. As a non-isolated (common ground) current module, it provides a cost-effective solution for high-density control loops where field signals share a common reference potential.

A critical performance feature of the AAI841-S50 is its ultra-fast 10 ms data update period, which is essential for high-speed process synchronization. The "S50" designation typically refers to the standard type with internal coating for environmental protection, suitable for diverse industrial settings.

Detailed Specifications

  • Module Identification: AAI841-S50

  • Channel Density: 8-channel input / 8-channel output

  • Signal Type: 4 to 20 mA DC (Current)

  • Isolation: Non-isolated (All channels share a common ground)

  • Measurement Precision: Input accuracy of ±16 µA

  • Control Precision: Output accuracy of ±48 µA

  • Data Refresh Rate: 10 ms cycle

  • Input Impedance: 250 Ω

  • Load Resistance (Output): 0 to 600 Ω

  • Transmitter Power Supply: 14.8 V DC (at 20 mA) to 26.4 V DC (at 0 mA)

  • Power Consumption: Max 450 mA at 5 V DC

  • Connectivity Options: Pressure clamp terminal, KS cable, or MIL connector interface

  • Environmental Protection: Standard conformal coating (S50 variant)

  • Module Weight: 1.3 kg

Module Comparison: S50 vs. H50 Variants

The AAI841-S50 is the standard version of this I/O card. In contrast, the "H" variant (AAI841-H50) often includes enhanced digital communication support, such as the HART protocol. For basic analog 4-20 mA monitoring and control where HART diagnostics are not required, the S50 model offers the same high-speed 10 ms refresh rate and accuracy while optimizing system costs.

Frequently Asked Questions

  • Does this module require external power for field transmitters?

    The AAI841-S50 includes an integrated power supply capable of providing at least 14.8 V at 20 mA, making it suitable for 2-wire loop-powered transmitters.

  • Can I use this module for high-speed PID control?

    Yes, the 10 ms update period makes it ideal for dynamic loops that require rapid response times.

  • What is the significance of the non-isolated design?

    Since channels share a common negative line, this module is best used when field devices are grounded at the same potential to avoid ground loop interference.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

Redundant Automation Systems: Ensuring Continuous Uptime in Critical Control Infrastructure

System reliability directly determines operational profitability across high stakes process industries. Modern industrial automation platforms must eliminate single points of failure to prevent catastrophic shutdowns. Deploying fault tolerant architecture safeguards complex facilities against unexpected hardware glitches, network disruptions, and maintenance outages.

Read more
Understanding Types of Noise in Electronic Circuits and Control Systems

Understanding Types of Noise in Electronic Circuits and Control Systems

Signal integrity directly determines measurement accuracy and loop stability across industrial automation environments. Electronic noise introduces unwanted stochastic interference into analog loops, sensor feedback lines, and digital fieldbus networks. Understanding how intrinsic electronic noise and external electromagnetic interference manifest allows control engineers to optimize signal conditioning and shield sensitive instrumentation effectively.

Read more
Why 24V DC Power Supplies Standardize Modern Industrial Automation

Why 24V DC Power Supplies Standardize Modern Industrial Automation

Industrial control cabinets worldwide rely on 24V DC as the universal power standard for field instrumentation, sensors, and controllers. Walk into any manufacturing plant, and you will find PLCs, human-machine interfaces (HMIs), and smart actuators running on extra-low voltage DC. Standardizing on 24V DC enhances operational safety, lowers cabinet footprint, and maintains steady control performance across factory networks.

Read more