PRODUCT SKU : 1900/65A-00-01-01-01-01

PRODUCT TYPE : Equipment Monitors

PRODUCT VENDOR : Bently Nevada


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

The Bently Nevada 1900/65A-00-01-01-01-01 is a general-purpose machinery monitor designed for continuous machinery protection and condition monitoring. It evaluates dynamic vibration, position, and thermal inputs to track machinery health and trigger automated alarm relays before critical failure occurs.

Input and Output Interface Configuration

The monitor provides four dedicated transducer inputs supporting accelerometers, velocity sensors, and proximity probes, alongside four temperature inputs compatible with thermocouples and RTDs. For supervisory control and record keeping, the hardware incorporates six relay outputs, four 4-20 mA analog recorder outputs, and one dedicated buffered output for direct raw signal diagnostics.

Connectivity, Options Breakdown, and Physical Dimensions

Equipped with Modbus communication protocols via Ethernet and RS232/RS485 serial interfaces, the module integrates seamlessly into plant automation networks. Operating within a compact enclosure measuring 19.6 cm x 16 cm x 8 cm and weighing 0.98 kg, the complete ordering code breaks down into the following option selections:

  • 00 (Power Option): 18 to 36 VDC
  • 01 (Display Option): Attached display (no cable)
  • 01 (Mounting Option): DIN rail mount
  • 01 (Approvals Option): Multiple approvals
  • 01 (Communications Option): Modbus via Ethernet and RS232/RS485 serial port
Parameter Specification
Model 1900/65A-00-01-01-01-01
Brand Bently Nevada
Product Category General Purpose Equipment Monitors
Supply Voltage 18 to 36 VDC
Display Type Attached display (no cable)
Mounting Option DIN rail mount
Approvals Multiple approvals
Transducer Inputs 4 channels (accelerometers, velocity sensors, proximity sensors)
Temperature Inputs 4 channels (thermocouples and RTDs)
Relay Outputs 6 channels
Recorder Outputs 4 channels (4-20 mA)
Buffered Output 1 dedicated channel
Communication Protocols Modbus via Ethernet and RS232/RS485
Dimensions 19.6 cm x 16 cm x 8 cm
Weight 0.98 kg

Frequently Asked Questions

Q: What power supply input voltage is required for this model configuration?

A: Option code -00 specifies a DC power supply operating range of 18 to 36 VDC.

Q: What field sensors can be connected to the monitor's input channels?

A: The four transducer channels support accelerometers, velocity sensors, and proximity probes, while the four temperature channels accept thermocouples and RTDs.

Q: What options are selected in the 1900/65A-00-01-01-01-01 part number?

A: This configuration features 18-36 VDC power (-00), an attached display (-01), DIN rail mounting (-01), multiple agency approvals (-01), and Modbus communication interfaces (-01).

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Why Programmable Logic Controllers Drop into Stop Mode: An Expert Analysis

Industrial automation systems rely heavily on Programmable Logic Controllers (PLCs) to maintain uninterrupted production. When a PLC unexpectedly shifts from Run to Stop mode, whole manufacturing lines stall.

As control systems evolve across modern factory automation, understanding the root causes of these interruptions helps engineers minimize costly downtime. This technical guide breaks down why PLCs trip into Stop mode and provides practical strategies to mitigate system faults.

Read more
Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Understanding Root Causes of Unplanned PLC Stop Mode in Industrial Automation

Modern Programmable Logic Controllers manage execution through distinct operational states: Run, Stop, Start-Up, and Hold. During power-up, a controller initializes memory registers within Stop mode before briefly transitioning to Start-Up mode. During this phase, internal self-diagnostics evaluate system integrity across hardware and user programs. If the controller detects no critical faults, it enters Run mode to execute the control program continuously. However, any severe system anomaly forces the CPU back into Stop mode immediately to prevent erratic machine behavior across the plant floor.

Read more
Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interface Design: Essential Guide to HMI Selection, Visualization, and Control System Integration

Human-Machine Interfaces (HMIs) serve as the primary operational window into complex industrial automation systems. Modern HMIs convert raw machine data into clear graphical displays, enabling operators to oversee entire manufacturing processes in real time. Instead of relying on physical control panels full of hardwired switches, engineers program interactive screens using intuitive graphics, dynamic color coding, and responsive touch interfaces. Over my 15 years in control systems engineering, I have observed HMIs transform from basic display screens into sophisticated command centers that drive operational efficiency across DCS and PLC environments.

Read more