Skip to content

What are you looking for?


You may also like

1715-TADOB8DE | Allen-Bradley | Termination Assembly | 8-Channel DO Duplex1715-TADOB8DE | Allen-Bradley | Termination Assembly | 8-Channel DO Duplex1715-TADOB8DE | Allen-Bradley | Termination Assembly | 8-Channel DO Duplex
1715-TADOB8DE | Allen-Bradley | Termination Assembly | 8-Channel DO Duplex
1715-TADOB8DE | Allen-Bradley | Termination Assembly | 8-Channel DO Duplex
1715-TADOB8DE | Allen-Bradley | Termination Assembly | 8-Channel DO Duplex

1715-TADOB8DE | Allen-Bradley | Termination Assembly | 8-Channel DO Duplex


Only 10 left - Selling fast

PRODUCT SKU : 1715-TADOB8DE

PRODUCT TYPE : Termination Assembly

PRODUCT VENDOR : Allen-Bradley


  • 100% Genuine Parts – Risk-Free 30-Day Returns
  • 1-Year Warranty & Expert Support for Every Order

Product Details

Product Description

The Allen-Bradley 1715-TADOB8DE Termination Assembly is engineered for 8-channel digital output duplex configurations, offering reliable signal termination, fuse protection, and stable performance in distributed I/O systems. Its design ensures dependable operation in industrial automation environments where redundancy and precision are critical.

Technical Specifications

  • Manufacturer: Allen-Bradley

  • Product Number: 1715-TADOB8DE

  • Product Type: Termination Assembly, 8-Channel DO Duplex

  • Fuse Rating: 50 mA per channel

  • Screw Torque: 0.5 N·m (0.37 lb·ft)

  • Screwdriver Width: Flathead 0.4 × 2.0 mm (0.0156 × 0.0781 in.)

  • Backplane Current: 0.5 A per channel at 18–32 VDC

  • Field Voltage Slew Rate (Max): 150 V/s

  • De-energized Output Voltage Slew Rate (Max): 12 V/ms

  • Energized Output Current Slew Rate (Max): 0.9 A/ms

  • System Power Dissipation: 3.0 W maximum

  • Field Loop Power Dissipation: 0.17 W per loop maximum

  • Isolation Voltage: 50 V continuous, basic insulation type (I/O ports to backplane); no isolation between individual I/O ports; type tested at 500 V AC for 60 seconds

  • Dimensions (W × H): 8.4 cm × 13.2 cm

  • Weight: 0.26 kg

Application Scenarios

  • Digital Output Control: Provides reliable termination for duplex digital output signals

  • Distributed I/O Systems: Ensures stable performance in redundant configurations

  • Industrial Automation: Suitable for manufacturing, process control, and safety-critical environments

FAQ

  • Q: What type of fuse protection is included?  A: Each channel is protected with a 50 mA fuse, ensuring fault isolation and reliability.

  • Q: Does the assembly provide isolation between channels?  A: No, there is no isolation between individual I/O ports. However, the assembly provides 50 V continuous isolation between I/O ports and the backplane.

  • Q: What is the maximum system power dissipation?  A: The system power dissipation is 3.0 W maximum, with 0.17 W per field loop.

  • Q: How does this model compare to the 1715-TADIF16?  A: The 1715-TADOB8DE is designed for digital output duplex applications, while the 1715-TADIF16 is intended for analog input duplex configurations.

Additional Information

  • 100% Genuine Parts: All products are original and authentic, ensuring reliable industrial performance.
  • 30-Day Refund Guarantee: Return any in-stock item within 30 days in original, unopened packaging for a full refund (excluding shipping and fees).
  • 12-Month Warranty: Covers defects in materials or workmanship; excludes misuse, normal wear, or unauthorized modifications.
  • Worldwide Shipping: We ship via USPS, UPS, FedEx, and DHL. Delivery times vary by country and may be subject to customs or import fees.
  • Support & Contact: Technical and warranty assistance is available anytime. Contact us here: Contact.
  • Purchase Guidance: Check product specifications and compatibility carefully before ordering to ensure proper application.




Recently Viewed Products

Tech & Buying Guide

Technical Insights, Installation Guides, and Buying Tips
Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Comprehensive Guide to Noise Types in Industrial Automation and Electronics

Signal integrity determines reliability in modern industrial automation. Unwanted electrical noise degrades sensor data, distorts 4-20 mA current loops, and drops fieldbus communications. Engineers working with PLC, DCS, and TSI systems must effectively mitigate these disturbances. This technical guide analyzes key internal and external noise sources affecting control systems.
Read more
Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Mitigating Emergency Stop Spurious Trips in Industrial Control Systems

Emergency stop (E-Stop) pushbuttons serve as vital safety devices in factory automation and process control plants. Functional safety standards mandate normally-closed (NC) contact blocks to ensure fail-safe operation during wiring breaks or power outages. However, mechanical degradation over time can trigger unexpected spurious trips, halting production lines without an actual emergency. Understanding the underlying causes of mechanical contact failure allows automation engineers to implement robust, fault-tolerant safety circuits.

Read more
Redundant Automation Systems: Maximizing Uptime in Critical Control Applications

Redundant Automation Systems: Maximizing Uptime in Critical Control Applications

Industrial automation relies on continuous operational stability to prevent catastrophic downtime and financial loss. While standard dictionary definitions treat redundancy as superfluous, industrial engineers consider redundant control architectures indispensable for high-availability systems. Implementing backup hardware ensures seamless takeover during primary equipment failures, protecting critical infrastructure across manufacturing and process industries.

Read more